Lafayette

PFAS monitoring results for a public water system in Georgia

GA2950002UCMR 5EPA monitoring data
31Highest PFOA result, ppt
56Highest PFOS result, ppt
0.542Highest Hazard Index
480Results
PWSID
GA2950002
State
Georgia
System type
community water system (CWS)
Population served
18,177
City
Lafayette
Counties
Walker County
Primary source water
surface water (purchased)
UCMR 5 sampling
2025-02-27 to 2025-12-01 · 5 entry point(s) · water types: GU;GW;SW
Service-area boundary
authoritative

PFOS ≥ 3 × its limit highest single result
PFOS ≥ 3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)3116.624
PFOS (ppt)5628.54
Hazard Index0.5420.2541.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Sampling history

Sampled 2025-02-27 to 2025-12-01 · 5 entry point(s) · water types: GU;GW;SW · 18 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2025-02-27Big Springs Water Plant (GU)SE1n/an/an/anone
2025-02-27Catoosa Utility District (GW)SE15.1<40.017none
2025-02-27Dixon Springs Water Plant (GW)SE1<4<40.007none
2025-02-27Lee School Road Plant (GU)SE1<4<40.006none
2025-02-27Walker County WA (SW)SE1n/an/an/anone
2025-04-16Big Springs Water Plant (GU)SE14.6<40.009none
2025-04-16Walker County WA (SW)SE131560.542PFDA 3, PFHpA 7.6, PFHxA 8, PFPeA 9.2
2025-06-04Big Springs Water Plant (GU)SE24.5<40.01none
2025-06-04Lee School Road Plant (GU)SE2<4<40.006none
2025-06-04Walker County WA (SW)SE224480.451PFHpA 6.1, PFHxA 6.6, PFPeA 7.5
2025-09-15Big Springs Water Plant (GU)SE3<4<40.011none
2025-09-15Catoosa Utility District (GW)SE2<4<40.01none
2025-09-15Dixon Springs Water Plant (GW)SE2<4<40.007none
2025-09-15Lee School Road Plant (GU)SE3<4<40.007none
2025-09-15Walker County WA (SW)SE34.3<40.009PFPeA 3.3
2025-12-01Big Springs Water Plant (GU)SE4<4<40.011none
2025-12-01Lee School Road Plant (GU)SE4<4<40.009none
2025-12-01Walker County WA (SW)SE47.2100.012PFHxA 3.6, PFPeA 5

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

480 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Big Springs Water Plant facility 03253 · sample point 302 · groundwater under the influence of surface water

CompoundMRL2025-02-27
SE1
2025-04-16
SE1
2025-06-04
SE2
2025-09-15
SE3
2025-12-01
SE4
PFBS3 ppt–18202223
PFOA4 ppt–4.64.5< 4< 4
11Cl-PF3OUdS5 ppt–< 5< 5< 5< 5
4:2 FTS3 ppt–< 3< 3< 3< 3
6:2 FTS5 ppt–< 5< 5< 5< 5
8:2 FTS5 ppt–< 5< 5< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2< 2< 2
ADONA3 ppt–< 3< 3< 3< 3
HFPO-DA5 ppt–< 5< 5< 5< 5
NEtFOSAA5 ppt< 5–< 5< 5< 5
NFDHA20 ppt–< 20< 20< 20< 20
NMeFOSAA6 ppt< 6–< 6< 6< 6
PFBA5 ppt–< 5< 5< 5< 5
PFDA3 ppt–< 3< 3< 3< 3
PFDoA3 ppt–< 3< 3< 3< 3
PFEESA3 ppt–< 3< 3< 3< 3
PFHpA3 ppt–< 3< 3< 3< 3
PFHpS3 ppt–< 3< 3< 3< 3
PFHxA3 ppt–< 3< 3< 3< 3
PFHxS3 ppt–< 3< 3< 3< 3
PFMBA3 ppt–< 3< 3< 3< 3
PFMPA4 ppt–< 4< 4< 4< 4
PFNA4 ppt–< 4< 4< 4< 4
PFOS4 ppt–< 4< 4< 4< 4
PFPeA3 ppt–< 3< 3< 3< 3
PFPeS4 ppt–< 4< 4< 4< 4
PFTA8 ppt< 8–< 8< 8< 8
PFTrDA7 ppt< 7–< 7< 7< 7
PFUnA2 ppt–< 2< 2< 2< 2
lithium9 µg/L< 9–< 9< 9< 9

Catoosa Utility District facility 14633 · sample point 305 · groundwater

CompoundMRL2025-02-27
SE1
2025-09-15
SE2
PFBS3 ppt3420
PFOA4 ppt5.1< 4
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Dixon Springs Water Plant facility 1460009 · sample point 303 · groundwater

CompoundMRL2025-02-27
SE1
2025-09-15
SE2
PFBS3 ppt1415
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Lee School Road Plant facility 03864 · sample point 306 · groundwater under the influence of surface water

CompoundMRL2025-02-27
SE1
2025-06-04
SE2
2025-09-15
SE3
2025-12-01
SE4
PFBS3 ppt13131517
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFBA5 ppt< 5< 5< 5< 5
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxA3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeA3 ppt< 3< 3< 3< 3
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

Walker County WA facility 14632 · sample point 304 · surface water

CompoundMRL2025-02-27
SE1
2025-04-16
SE1
2025-06-04
SE2
2025-09-15
SE3
2025-12-01
SE4
PFBS3 ppt–44411924
PFDA3 ppt–3< 3< 3< 3
PFHpA3 ppt–7.66.1< 3< 3
PFHxA3 ppt–86.6< 33.6
PFHxS3 ppt–5.24.3< 3< 3
PFOA4 ppt–31244.37.2
PFOS4 ppt–5648< 410
PFPeA3 ppt–9.27.53.35
11Cl-PF3OUdS5 ppt–< 5< 5< 5< 5
4:2 FTS3 ppt–< 3< 3< 3< 3
6:2 FTS5 ppt–< 5< 5< 5< 5
8:2 FTS5 ppt–< 5< 5< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2< 2< 2
ADONA3 ppt–< 3< 3< 3< 3
HFPO-DA5 ppt–< 5< 5< 5< 5
NEtFOSAA5 ppt< 5–< 5< 5< 5
NFDHA20 ppt–< 20< 20< 20< 20
NMeFOSAA6 ppt< 6–< 6< 6< 6
PFBA5 ppt–< 5< 5< 5< 5
PFDoA3 ppt–< 3< 3< 3< 3
PFEESA3 ppt–< 3< 3< 3< 3
PFHpS3 ppt–< 3< 3< 3< 3
PFMBA3 ppt–< 3< 3< 3< 3
PFMPA4 ppt–< 4< 4< 4< 4
PFNA4 ppt–< 4< 4< 4< 4
PFPeS4 ppt–< 4< 4< 4< 4
PFTA8 ppt< 8–< 8< 8< 8
PFTrDA7 ppt< 7–< 7< 7< 7
PFUnA2 ppt–< 2< 2< 2< 2
lithium9 µg/L< 9–< 9< 9< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBS16100%44
2025-04-16
22–2219234144
PFOA1644%31
2025-04-16
5.04–7.29<MRL4.62431
PFPeA1625%9.2
2025-04-16
1.56–3.81<MRL<MRL7.59.2
PFHxA1619%8
2025-04-16
1.14–3.58<MRL<MRL6.68
PFOS1619%56
2025-04-16
7.12–10.38<MRL<MRL4856
PFHpA1612%7.6
2025-04-16
0.86–3.48<MRL<MRL6.17.6
PFHxS1612%5.2
2025-04-16
0.59–3.22<MRL<MRL4.35.2
PFDA166%3
2025-04-16
0.19–3<MRL<MRL<MRL3

Never detected (22): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFDoA, PFEESA, PFHpS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-17; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build e0e919e2a26a · 2026-10-18T04:09Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.