Holliday Water Company

PFAS monitoring results for a public water system in Utah

UTAH18010UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
<MRLHighest PFOS result, ppt
0Highest Hazard Index
480Results
PWSID
UTAH18010
State
Utah
System type
community water system (CWS)
Population served
15,000
City
Salt Lake City
Counties
Salt Lake County
Primary source water
surface water (purchased)
UCMR 5 sampling
2023-07-19 to 2024-07-10 · 6 entry point(s) · water types: GU;GW;MX
Service-area boundary
authoritative

No PFAS detected highest single result
No PFAS detected worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

  • Salt Lake City Water System (UTAH18026)
    Seller's highest results: PFOA <MRL · PFOS 7.1 ppt · HI 1.82 · detected: PFHxA;PFHxS;PFOS;PFPeA

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)<MRL04
Hazard Index001.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Utah PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; follows federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2023-07-19 to 2024-07-10 · 6 entry point(s) · water types: GU;GW;MX · 22 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2023-07-191887 E. 4500 S. Well (GW)SE1n/an/an/alithium 27.5 µg/L
2023-07-192000 E. Gunderson Well (GW)SE1n/an/an/alithium 27.1 µg/L
2023-07-194360 Wander Ln. Well (GW)SE1n/an/an/alithium 11.8 µg/L
2023-07-19Liveoak Cir. Well #4 (GW)SE1n/an/an/anone
2023-07-19Main Spring- Lower Spring (GU)SE1n/an/an/anone
2023-07-19Salt Lake City Water Intertie (MX)SE1n/an/an/anone
2023-08-311887 E. 4500 S. Well (GW)SE1<4<40none
2023-08-312000 E. Gunderson Well (GW)SE1<4<40none
2023-08-314360 Wander Ln. Well (GW)SE1<4<40none
2023-08-31Liveoak Cir. Well #4 (GW)SE1<4<40none
2023-08-31Main Spring- Lower Spring (GU)SE1<4<40none
2023-08-31Salt Lake City Water Intertie (MX)SE1<4<40none
2023-10-25Main Spring- Lower Spring (GU)SE2<4<40none
2023-10-25Salt Lake City Water Intertie (MX)SE2<4<40lithium 11.9 µg/L
2024-01-23Main Spring- Lower Spring (GU)SE3<4<40none
2024-01-23Salt Lake City Water Intertie (MX)SE3<4<40lithium 14.6 µg/L
2024-04-17Main Spring- Lower Spring (GU)SE4<4<40none
2024-04-17Salt Lake City Water Intertie (MX)SE4<4<40none
2024-07-101887 E. 4500 S. Well (GW)SE2<4<40lithium 29 µg/L
2024-07-102000 E. Gunderson Well (GW)SE2<4<40lithium 30.5 µg/L
2024-07-104360 Wander Ln. Well (GW)SE2<4<40lithium 12.4 µg/L
2024-07-10Liveoak Cir. Well #4 (GW)SE2<4<40none

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

480 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

1887 E. 4500 S. Well facility 00002 · sample point WS002 · groundwater

CompoundMRL2023-07-19
SE1
2023-08-31
SE1
2024-07-10
SE2
11Cl-PF3OUdS5 ppt–< 5< 5
4:2 FTS3 ppt–< 3< 3
6:2 FTS5 ppt–< 5< 5
8:2 FTS5 ppt–< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2
ADONA3 ppt–< 3< 3
HFPO-DA5 ppt–< 5< 5
NEtFOSAA5 ppt–< 5< 5
NFDHA20 ppt–< 20< 20
NMeFOSAA6 ppt–< 6< 6
PFBA5 ppt–< 5< 5
PFBS3 ppt–< 3< 3
PFDA3 ppt–< 3< 3
PFDoA3 ppt–< 3< 3
PFEESA3 ppt–< 3< 3
PFHpA3 ppt–< 3< 3
PFHpS3 ppt–< 3< 3
PFHxA3 ppt–< 3< 3
PFHxS3 ppt–< 3< 3
PFMBA3 ppt–< 3< 3
PFMPA4 ppt–< 4< 4
PFNA4 ppt–< 4< 4
PFOA4 ppt–< 4< 4
PFOS4 ppt–< 4< 4
PFPeA3 ppt–< 3< 3
PFPeS4 ppt–< 4< 4
PFTA8 ppt–< 8< 8
PFTrDA7 ppt–< 7< 7
PFUnA2 ppt–< 2< 2
lithium9 µg/L27.5–29

2000 E. Gunderson Well facility 00004 · sample point WS004 · groundwater

CompoundMRL2023-07-19
SE1
2023-08-31
SE1
2024-07-10
SE2
11Cl-PF3OUdS5 ppt–< 5< 5
4:2 FTS3 ppt–< 3< 3
6:2 FTS5 ppt–< 5< 5
8:2 FTS5 ppt–< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2
ADONA3 ppt–< 3< 3
HFPO-DA5 ppt–< 5< 5
NEtFOSAA5 ppt–< 5< 5
NFDHA20 ppt–< 20< 20
NMeFOSAA6 ppt–< 6< 6
PFBA5 ppt–< 5< 5
PFBS3 ppt–< 3< 3
PFDA3 ppt–< 3< 3
PFDoA3 ppt–< 3< 3
PFEESA3 ppt–< 3< 3
PFHpA3 ppt–< 3< 3
PFHpS3 ppt–< 3< 3
PFHxA3 ppt–< 3< 3
PFHxS3 ppt–< 3< 3
PFMBA3 ppt–< 3< 3
PFMPA4 ppt–< 4< 4
PFNA4 ppt–< 4< 4
PFOA4 ppt–< 4< 4
PFOS4 ppt–< 4< 4
PFPeA3 ppt–< 3< 3
PFPeS4 ppt–< 4< 4
PFTA8 ppt–< 8< 8
PFTrDA7 ppt–< 7< 7
PFUnA2 ppt–< 2< 2
lithium9 µg/L27.1–30.5

4360 Wander Ln. Well facility 00003 · sample point WS003 · groundwater

CompoundMRL2023-07-19
SE1
2023-08-31
SE1
2024-07-10
SE2
11Cl-PF3OUdS5 ppt–< 5< 5
4:2 FTS3 ppt–< 3< 3
6:2 FTS5 ppt–< 5< 5
8:2 FTS5 ppt–< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2
ADONA3 ppt–< 3< 3
HFPO-DA5 ppt–< 5< 5
NEtFOSAA5 ppt–< 5< 5
NFDHA20 ppt–< 20< 20
NMeFOSAA6 ppt–< 6< 6
PFBA5 ppt–< 5< 5
PFBS3 ppt–< 3< 3
PFDA3 ppt–< 3< 3
PFDoA3 ppt–< 3< 3
PFEESA3 ppt–< 3< 3
PFHpA3 ppt–< 3< 3
PFHpS3 ppt–< 3< 3
PFHxA3 ppt–< 3< 3
PFHxS3 ppt–< 3< 3
PFMBA3 ppt–< 3< 3
PFMPA4 ppt–< 4< 4
PFNA4 ppt–< 4< 4
PFOA4 ppt–< 4< 4
PFOS4 ppt–< 4< 4
PFPeA3 ppt–< 3< 3
PFPeS4 ppt–< 4< 4
PFTA8 ppt–< 8< 8
PFTrDA7 ppt–< 7< 7
PFUnA2 ppt–< 2< 2
lithium9 µg/L11.8–12.4

Liveoak Cir. Well #4 facility 00007 · sample point WS007 · groundwater

CompoundMRL2023-07-19
SE1
2023-08-31
SE1
2024-07-10
SE2
11Cl-PF3OUdS5 ppt–< 5< 5
4:2 FTS3 ppt–< 3< 3
6:2 FTS5 ppt–< 5< 5
8:2 FTS5 ppt–< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2
ADONA3 ppt–< 3< 3
HFPO-DA5 ppt–< 5< 5
NEtFOSAA5 ppt–< 5< 5
NFDHA20 ppt–< 20< 20
NMeFOSAA6 ppt–< 6< 6
PFBA5 ppt–< 5< 5
PFBS3 ppt–< 3< 3
PFDA3 ppt–< 3< 3
PFDoA3 ppt–< 3< 3
PFEESA3 ppt–< 3< 3
PFHpA3 ppt–< 3< 3
PFHpS3 ppt–< 3< 3
PFHxA3 ppt–< 3< 3
PFHxS3 ppt–< 3< 3
PFMBA3 ppt–< 3< 3
PFMPA4 ppt–< 4< 4
PFNA4 ppt–< 4< 4
PFOA4 ppt–< 4< 4
PFOS4 ppt–< 4< 4
PFPeA3 ppt–< 3< 3
PFPeS4 ppt–< 4< 4
PFTA8 ppt–< 8< 8
PFTrDA7 ppt–< 7< 7
PFUnA2 ppt–< 2< 2
lithium9 µg/L< 9–< 9

Main Spring- Lower Spring facility 00005 · sample point WS005 · groundwater under the influence of surface water

CompoundMRL2023-07-19
SE1
2023-08-31
SE1
2023-10-25
SE2
2024-01-23
SE3
2024-04-17
SE4
11Cl-PF3OUdS5 ppt–< 5< 5< 5< 5
4:2 FTS3 ppt–< 3< 3< 3< 3
6:2 FTS5 ppt–< 5< 5< 5< 5
8:2 FTS5 ppt–< 5< 5< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2< 2< 2
ADONA3 ppt–< 3< 3< 3< 3
HFPO-DA5 ppt–< 5< 5< 5< 5
NEtFOSAA5 ppt–< 5< 5< 5< 5
NFDHA20 ppt–< 20< 20< 20< 20
NMeFOSAA6 ppt–< 6< 6< 6< 6
PFBA5 ppt–< 5< 5< 5< 5
PFBS3 ppt–< 3< 3< 3< 3
PFDA3 ppt–< 3< 3< 3< 3
PFDoA3 ppt–< 3< 3< 3< 3
PFEESA3 ppt–< 3< 3< 3< 3
PFHpA3 ppt–< 3< 3< 3< 3
PFHpS3 ppt–< 3< 3< 3< 3
PFHxA3 ppt–< 3< 3< 3< 3
PFHxS3 ppt–< 3< 3< 3< 3
PFMBA3 ppt–< 3< 3< 3< 3
PFMPA4 ppt–< 4< 4< 4< 4
PFNA4 ppt–< 4< 4< 4< 4
PFOA4 ppt–< 4< 4< 4< 4
PFOS4 ppt–< 4< 4< 4< 4
PFPeA3 ppt–< 3< 3< 3< 3
PFPeS4 ppt–< 4< 4< 4< 4
PFTA8 ppt–< 8< 8< 8< 8
PFTrDA7 ppt–< 7< 7< 7< 7
PFUnA2 ppt–< 2< 2< 2< 2
lithium9 µg/L< 9–< 9< 9< 9

Salt Lake City Water Intertie facility 05772 · sample point WS001 · MX

CompoundMRL2023-07-19
SE1
2023-08-31
SE1
2023-10-25
SE2
2024-01-23
SE3
2024-04-17
SE4
11Cl-PF3OUdS5 ppt–< 5< 5< 5< 5
4:2 FTS3 ppt–< 3< 3< 3< 3
6:2 FTS5 ppt–< 5< 5< 5< 5
8:2 FTS5 ppt–< 5< 5< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2< 2< 2
ADONA3 ppt–< 3< 3< 3< 3
HFPO-DA5 ppt–< 5< 5< 5< 5
NEtFOSAA5 ppt–< 5< 5< 5< 5
NFDHA20 ppt–< 20< 20< 20< 20
NMeFOSAA6 ppt–< 6< 6< 6< 6
PFBA5 ppt–< 5< 5< 5< 5
PFBS3 ppt–< 3< 3< 3< 3
PFDA3 ppt–< 3< 3< 3< 3
PFDoA3 ppt–< 3< 3< 3< 3
PFEESA3 ppt–< 3< 3< 3< 3
PFHpA3 ppt–< 3< 3< 3< 3
PFHpS3 ppt–< 3< 3< 3< 3
PFHxA3 ppt–< 3< 3< 3< 3
PFHxS3 ppt–< 3< 3< 3< 3
PFMBA3 ppt–< 3< 3< 3< 3
PFMPA4 ppt–< 4< 4< 4< 4
PFNA4 ppt–< 4< 4< 4< 4
PFOA4 ppt–< 4< 4< 4< 4
PFOS4 ppt–< 4< 4< 4< 4
PFPeA3 ppt–< 3< 3< 3< 3
PFPeS4 ppt–< 4< 4< 4< 4
PFTA8 ppt–< 8< 8< 8< 8
PFTrDA7 ppt–< 7< 7< 7< 7
PFUnA2 ppt–< 2< 2< 2< 2
lithium9 µg/L< 9–11.914.6< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
lithium1650%30.5
2024-07-10
10.3–14.8<MRL14.62930.5

Never detected (29): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFHxA, PFHxS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-23 to 2026-06-09; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build d49524ed2d68 · 2026-10-18T04:07Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.