- PWSID
- UTAH06009
- State
- Utah
- System type
- community water system (CWS)
- Population served
- 10,565
- City
- Bountiful
- Counties
- Davis County
- Primary source water
- surface water (purchased)
- UCMR 5 sampling
- 2023-03-14 to 2023-11-21 · 5 entry point(s) · water types: GW
- Service-area boundary
- authoritative
Hazard Index 1–3 × its limit highest single result
Hazard Index below its limit worst entry-point average
Open on the Utah map · All Utah systems · All results
These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.
Water purchased from
- Weber Basin Wcd - South (UTAH06013)
Seller not monitored under UCMR 5.
Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.
Compared with EPA's 2024 values
| Highest single result | Worst entry-point average* | Limit | |
|---|---|---|---|
| PFOA (ppt) | <MRL | 0 | 4 |
| PFOS (ppt) | <MRL | 0 | 4 |
| Hazard Index | 1.202 | 0.745 | 1.0† |
“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).
No Utah PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; follows federal NPDWR (BCLP state survey, Jan 2026).
Sampling history
Sampled 2023-03-14 to 2023-11-21 · 5 entry point(s) · water types: GW · 13 sampling visits. PFAS in ppt (ng/L).
| Date | Entry point | Event | PFOA | PFOS | HI | Other detections |
|---|---|---|---|---|---|---|
| 2023-03-14 | SOUTH DAVIS WATER DISTRICT (GW) | SE1 | <4 | <4 | 0.64 | PFHxA 3.4, PFPeA 4.2 |
| 2023-03-14 | SOUTH DAVIS WATER DISTRICT (GW) | SE1 | <4 | <4 | 0.57 | none |
| 2023-03-14 | SOUTH DAVIS WATER DISTRICT (GW) | SE1 | <4 | <4 | 0.73 | PFHxA 3.4, PFPeA 4.6 |
| 2023-03-14 | SOUTH DAVIS WATER DISTRICT (GW) | SE1 | <4 | <4 | 0.37 | none |
| 2023-03-14 | SOUTH DAVIS WATER DISTRICT (GW) | SE1 | <4 | <4 | 0 | none |
| 2023-09-27 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | <4 | <4 | 0.85 | PFHxA 3.8, PFPeA 4, lithium 21 µg/L |
| 2023-09-27 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | <4 | <4 | 0 | lithium 17 µg/L |
| 2023-09-27 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | <4 | <4 | 0 | lithium 11 µg/L |
| 2023-09-27 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | <4 | <4 | 0 | lithium 17 µg/L |
| 2023-09-27 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | n/a | n/a | n/a | lithium 23 µg/L |
| 2023-11-21 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | <4 | <4 | 1.202 | PFHxA 4.6, PFPeA 5.6 |
| 2023-11-21 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | n/a | n/a | n/a | none |
| 2023-11-21 | SOUTH DAVIS WATER DISTRICT (GW) | SE2 | n/a | n/a | n/a | none |
“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).
All results by entry point
300 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.
SOUTH DAVIS WATER DISTRICT facility EP005 · sample point EP005 · groundwater
| Compound | MRL | 2023-03-14 SE1 | 2023-09-27 SE2 | 2023-11-21 SE2 |
|---|---|---|---|---|
| PFHxA | 3 ppt | 3.4 | 3.8 | – |
| PFHxS | 3 ppt | 6.4 | 8.5 | – |
| PFPeA | 3 ppt | 4.2 | 4 | – |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | – |
| 4:2 FTS | 3 ppt | < 3 | < 3 | – |
| 6:2 FTS | 5 ppt | < 5 | < 5 | – |
| 8:2 FTS | 5 ppt | < 5 | < 5 | – |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | – |
| ADONA | 3 ppt | < 3 | < 3 | – |
| HFPO-DA | 5 ppt | < 5 | < 5 | – |
| NEtFOSAA | 5 ppt | < 5 | – | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | – |
| NMeFOSAA | 6 ppt | < 6 | – | < 6 |
| PFBA | 5 ppt | < 5 | < 5 | – |
| PFBS | 3 ppt | < 3 | < 3 | – |
| PFDA | 3 ppt | < 3 | < 3 | – |
| PFDoA | 3 ppt | < 3 | < 3 | – |
| PFEESA | 3 ppt | < 3 | < 3 | – |
| PFHpA | 3 ppt | < 3 | < 3 | – |
| PFHpS | 3 ppt | < 3 | < 3 | – |
| PFMBA | 3 ppt | < 3 | < 3 | – |
| PFMPA | 4 ppt | < 4 | < 4 | – |
| PFNA | 4 ppt | < 4 | < 4 | – |
| PFOA | 4 ppt | < 4 | < 4 | – |
| PFOS | 4 ppt | < 4 | < 4 | – |
| PFPeS | 4 ppt | < 4 | < 4 | – |
| PFTA | 8 ppt | < 8 | – | < 8 |
| PFTrDA | 7 ppt | < 7 | – | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | – |
| lithium | 9 µg/L | < 9 | 21 | – |
SOUTH DAVIS WATER DISTRICT facility SS080 · sample point SS080 · groundwater
| Compound | MRL | 2023-03-14 SE1 | 2023-09-27 SE2 |
|---|---|---|---|
| PFHxS | 3 ppt | 5.7 | < 3 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 |
| PFBA | 5 ppt | < 5 | < 5 |
| PFBS | 3 ppt | < 3 | < 3 |
| PFDA | 3 ppt | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 |
| PFHpA | 3 ppt | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 |
| PFHxA | 3 ppt | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 |
| PFOA | 4 ppt | < 4 | < 4 |
| PFOS | 4 ppt | < 4 | < 4 |
| PFPeA | 3 ppt | < 3 | < 3 |
| PFPeS | 4 ppt | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | 17 |
SOUTH DAVIS WATER DISTRICT facility TP004 · sample point TP004 · groundwater
| Compound | MRL | 2023-03-14 SE1 | 2023-09-27 SE2 | 2023-11-21 SE2 |
|---|---|---|---|---|
| PFHxA | 3 ppt | 3.4 | < 3 | – |
| PFHxS | 3 ppt | 7.3 | < 3 | – |
| PFPeA | 3 ppt | 4.6 | < 3 | – |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | – |
| 4:2 FTS | 3 ppt | < 3 | < 3 | – |
| 6:2 FTS | 5 ppt | < 5 | < 5 | – |
| 8:2 FTS | 5 ppt | < 5 | < 5 | – |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | – |
| ADONA | 3 ppt | < 3 | < 3 | – |
| HFPO-DA | 5 ppt | < 5 | < 5 | – |
| NEtFOSAA | 5 ppt | < 5 | – | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | – |
| NMeFOSAA | 6 ppt | < 6 | – | < 6 |
| PFBA | 5 ppt | < 5 | < 5 | – |
| PFBS | 3 ppt | < 3 | < 3 | – |
| PFDA | 3 ppt | < 3 | < 3 | – |
| PFDoA | 3 ppt | < 3 | < 3 | – |
| PFEESA | 3 ppt | < 3 | < 3 | – |
| PFHpA | 3 ppt | < 3 | < 3 | – |
| PFHpS | 3 ppt | < 3 | < 3 | – |
| PFMBA | 3 ppt | < 3 | < 3 | – |
| PFMPA | 4 ppt | < 4 | < 4 | – |
| PFNA | 4 ppt | < 4 | < 4 | – |
| PFOA | 4 ppt | < 4 | < 4 | – |
| PFOS | 4 ppt | < 4 | < 4 | – |
| PFPeS | 4 ppt | < 4 | < 4 | – |
| PFTA | 8 ppt | < 8 | – | < 8 |
| PFTrDA | 7 ppt | < 7 | – | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | – |
| lithium | 9 µg/L | < 9 | 11 | – |
SOUTH DAVIS WATER DISTRICT facility TP005 · sample point TP005 · groundwater
| Compound | MRL | 2023-03-14 SE1 | 2023-09-27 SE2 |
|---|---|---|---|
| PFHxS | 3 ppt | 3.7 | < 3 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 |
| PFBA | 5 ppt | < 5 | < 5 |
| PFBS | 3 ppt | < 3 | < 3 |
| PFDA | 3 ppt | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 |
| PFHpA | 3 ppt | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 |
| PFHxA | 3 ppt | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 |
| PFOA | 4 ppt | < 4 | < 4 |
| PFOS | 4 ppt | < 4 | < 4 |
| PFPeA | 3 ppt | < 3 | < 3 |
| PFPeS | 4 ppt | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | 17 |
SOUTH DAVIS WATER DISTRICT facility TP009 · sample point EP009 · groundwater
| Compound | MRL | 2023-03-14 SE1 | 2023-09-27 SE2 | 2023-11-21 SE2 |
|---|---|---|---|---|
| PFBS | 3 ppt | < 3 | – | 3.1 |
| PFHxA | 3 ppt | < 3 | – | 4.6 |
| PFHxS | 3 ppt | < 3 | – | 12 |
| PFPeA | 3 ppt | < 3 | – | 5.6 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | – | < 5 |
| 4:2 FTS | 3 ppt | < 3 | – | < 3 |
| 6:2 FTS | 5 ppt | < 5 | – | < 5 |
| 8:2 FTS | 5 ppt | < 5 | – | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | – | < 2 |
| ADONA | 3 ppt | < 3 | – | < 3 |
| HFPO-DA | 5 ppt | < 5 | – | < 5 |
| NEtFOSAA | 5 ppt | < 5 | – | < 5 |
| NFDHA | 20 ppt | < 20 | – | < 20 |
| NMeFOSAA | 6 ppt | < 6 | – | < 6 |
| PFBA | 5 ppt | < 5 | – | < 5 |
| PFDA | 3 ppt | < 3 | – | < 3 |
| PFDoA | 3 ppt | < 3 | – | < 3 |
| PFEESA | 3 ppt | < 3 | – | < 3 |
| PFHpA | 3 ppt | < 3 | – | < 3 |
| PFHpS | 3 ppt | < 3 | – | < 3 |
| PFMBA | 3 ppt | < 3 | – | < 3 |
| PFMPA | 4 ppt | < 4 | – | < 4 |
| PFNA | 4 ppt | < 4 | – | < 4 |
| PFOA | 4 ppt | < 4 | – | < 4 |
| PFOS | 4 ppt | < 4 | – | < 4 |
| PFPeS | 4 ppt | < 4 | – | < 4 |
| PFTA | 8 ppt | < 8 | – | < 8 |
| PFTrDA | 7 ppt | < 7 | – | < 7 |
| PFUnA | 2 ppt | < 2 | – | < 2 |
| lithium | 9 µg/L | < 9 | 23 | – |
Statistics by compound
| Compound | Results | Detected | Highest (date) | Mean bounds | KM median | P75 | P90 | P95 |
|---|---|---|---|---|---|---|---|---|
| PFHxS | 10 | 60% | 12 2023-11-21 | 4.36–5.56 | 3.7 | 7.3 | 8.5 | 12 |
| lithium | 10 | 50% | 23 2023-09-27 | 8.9–13.4 | <MRL | 17 | 21 | 23 |
| PFHxA | 10 | 40% | 4.6 2023-11-21 | 1.52–3.32 | <MRL | 3.4 | 3.8 | 4.6 |
| PFPeA | 10 | 40% | 5.6 2023-11-21 | 1.84–3.64 | <MRL | 4.2 | 4.6 | 5.6 |
| PFBS | 10 | 10% | 3.1 2023-11-21 | 0.31–3.01 | <MRL | <MRL | <MRL | 3.1 |
Never detected (25): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeS, PFTA, PFTrDA, PFUnA.
Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.
Sources
- EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-23 to 2026-06-09; data summary dated Jul 2026)
- EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
- EPA Public Water System Service Areas v3 (Mar 2026)
- US Census Bureau cartographic boundary counties 1:500k, 2024
- EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+
Data build d49524ed2d68 · 2026-10-18T04:07Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.