Austins Colony

PFAS monitoring results for a public water system in Texas

TX2270255UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
<MRLHighest PFOS result, ppt
0.422Highest Hazard Index
120Results
PWSID
TX2270255
State
Texas
System type
community water system (CWS)
Population served
9,987
City
Austin
Counties
Travis County
Primary source water
groundwater
UCMR 5 sampling
2025-06-23 to 2025-12-16 · 2 entry point(s) · water types: GW
Service-area boundary
authoritative

Hazard Index below its limit highest single result
Hazard Index below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)<MRL04
Hazard Index0.4220.2121.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Texas PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; TCEQ implementing federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2025-06-23 to 2025-12-16 · 2 entry point(s) · water types: GW · 4 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2025-06-23GW FROM 130 REGIONAL WSC (GW)SE1<4<40lithium 12 µg/L
2025-06-23GW FROM MUNICIPAL GW SOLUTIONS (GW)SE1<4<40.422lithium 21 µg/L
2025-12-16GW FROM 130 REGIONAL WSC (GW)SE2<4<40lithium 12 µg/L
2025-12-16GW FROM MUNICIPAL GW SOLUTIONS (GW)SE2<4<40.003PFBA 5, PFHxA 3.7, PFPeA 12, lithium 19 µg/L

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

120 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

GW FROM 130 REGIONAL WSC facility P2270255B · sample point EP003 · groundwater

CompoundMRL2025-06-23
SE1
2025-12-16
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L1212

GW FROM MUNICIPAL GW SOLUTIONS facility P2270255A · sample point EP004 · groundwater

CompoundMRL2025-06-23
SE1
2025-12-16
SE2
PFBA5 ppt< 55
PFBS3 ppt3.75.9
PFHxA3 ppt< 33.7
PFHxS3 ppt4.2< 3
PFPeA3 ppt< 312
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L2119

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
lithium4100%21
2025-06-23
16–1612192121
PFBS450%5.9
2025-12-16
2.4–3.9<MRL3.75.95.9
PFBA425%5
2025-12-16
1.25–5<MRL<MRL55
PFHxA425%3.7
2025-12-16
0.93–3.17<MRL<MRL3.73.7
PFHxS425%4.2
2025-06-23
1.05–3.3<MRL<MRL4.24.2
PFPeA425%12
2025-12-16
3–5.25<MRL<MRL1212

Never detected (24): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-16; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build a6f3d99247ed · 2026-10-18T04:13Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.