City Of Fort Worth

PFAS monitoring results for a public water system in Texas

TX2200012UCMR 5EPA monitoring data
8.3Highest PFOA result, ppt
7.3Highest PFOS result, ppt
2.583Highest Hazard Index
600Results
PWSID
TX2200012
State
Texas
System type
community water system (CWS)
Population served
955,900
City
Fort Worth
Counties
Denton County, Parker County, Tarrant County, Wise County
Primary source water
surface water
UCMR 5 sampling
2023-01-23 to 2024-01-24 · 5 entry point(s) · water types: SW
Service-area boundary
authoritative

Hazard Index 1–3 × its limit highest single result
Hazard Index 1–3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)8.35.94
PFOS (ppt)7.36.174
Hazard Index2.5831.6121.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Texas PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; TCEQ implementing federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2023-01-23 to 2024-01-24 · 5 entry point(s) · water types: SW · 20 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2023-01-23Eagle Mountain WTP (SW)SE1<4<40PFBA 5.5
2023-01-23Rolling Hills WTP (SW)SE1<4<40PFBA 7.3, PFPeA 3.3
2023-01-23South Holly WTP (SW)SE14.241.292PFBA 6.8, PFHxA 6.6, PFPeA 4.3
2023-01-23Westside Water TP (SW)SE1<4<40PFBA 5.5, PFPeA 3.2
2023-04-10Eagle Mountain WTP (SW)SE2<4<40PFBA 7.6, PFPeA 3.6
2023-04-10North Holly WTP (SW)SE17.97.32.492PFBA 8.2, PFHxA 10, PFPeA 6
2023-04-10Rolling Hills WTP (SW)SE2<4<40PFBA 6.8, PFHxA 3.3, PFPeA 3.5
2023-04-10South Holly WTP (SW)SE28.372.583PFBA 8.7, PFHxA 10.6, PFPeA 6.2
2023-04-10Westside Water TP (SW)SE2<4<40PFBA 7.2, PFHxA 3.9, PFPeA 4.2
2023-07-24Eagle Mountain WTP (SW)SE3<4<40PFBA 7.5, PFHxA 3, PFPeA 3.8
2023-07-24North Holly WTP (SW)SE255.41.222PFBA 9, PFHxA 6.8, PFPeA 4.8
2023-07-24Rolling Hills WTP (SW)SE3<4<40.002PFBA 6.3, PFHxA 3.1, PFPeA 3.5
2023-07-24South Holly WTP (SW)SE34.95.60.852PFBA 8.6, PFHxA 5.7, PFPeA 5
2023-07-24Westside Water TP (SW)SE3<4<40.002PFBA 6.6, PFHxA 3.5, PFPeA 4.1
2023-10-09Eagle Mountain WTP (SW)SE4<4<40PFBA 8.3, PFHxA 3.5, PFPeA 3.9
2023-10-09North Holly WTP (SW)SE34.550.812PFBA 10, PFHxA 6, PFPeA 5
2023-10-09Rolling Hills WTP (SW)SE4<4<40PFBA 7.4, PFHxA 3.7, PFPeA 4.1
2023-10-09South Holly WTP (SW)SE44.74.60.792PFBA 9.7, PFHxA 5.8, PFPeA 5.1
2023-10-09Westside Water TP (SW)SE4<4<40PFBA 6.9, PFHxA 3.4, PFPeA 3.7
2024-01-24North Holly WTP (SW)SE46.271.922PFBA 7.3, PFHxA 8.4, PFPeA 5.4

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

600 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Eagle Mountain WTP facility 58297 · sample point EP005MC4 · surface water

CompoundMRL2023-01-23
SE1
2023-04-10
SE2
2023-07-24
SE3
2023-10-09
SE4
PFBA5 ppt5.57.67.58.3
PFHxA3 ppt< 3< 333.5
PFPeA3 ppt< 33.63.83.9
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFBS3 ppt< 3< 3< 3< 3
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

North Holly WTP facility 58294 · sample point EP001MC1 · surface water

CompoundMRL2023-04-10
SE1
2023-07-24
SE2
2023-10-09
SE3
2024-01-24
SE4
PFBA5 ppt8.29107.3
PFBS3 ppt4.944.14.9
PFHxA3 ppt106.868.4
PFHxS3 ppt24.912.28.119.2
PFOA4 ppt7.954.56.2
PFOS4 ppt7.35.457
PFPeA3 ppt64.855.4
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

Rolling Hills WTP facility 58296 · sample point EP004MC3 · surface water

CompoundMRL2023-01-23
SE1
2023-04-10
SE2
2023-07-24
SE3
2023-10-09
SE4
PFBA5 ppt7.36.86.37.4
PFBS3 ppt< 3< 33.3< 3
PFHxA3 ppt< 33.33.13.7
PFPeA3 ppt3.33.53.54.1
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

South Holly WTP facility 58295 · sample point EP003MC2 · surface water

CompoundMRL2023-01-23
SE1
2023-04-10
SE2
2023-07-24
SE3
2023-10-09
SE4
PFBA5 ppt6.88.78.69.7
PFBS3 ppt3.54.94.94.2
PFHxA3 ppt6.610.65.75.8
PFHxS3 ppt12.925.88.57.9
PFOA4 ppt4.28.34.94.7
PFOS4 ppt475.64.6
PFPeA3 ppt4.36.255.1
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

Westside Water TP facility 21876 · sample point EP006MC5 · surface water

CompoundMRL2023-01-23
SE1
2023-04-10
SE2
2023-07-24
SE3
2023-10-09
SE4
PFBA5 ppt5.57.26.66.9
PFBS3 ppt< 3< 33.2< 3
PFHxA3 ppt< 33.93.53.4
PFPeA3 ppt3.24.24.13.7
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBA20100%10
2023-10-09
7.56–7.567.38.399.7
PFPeA2095%6.2
2023-04-10
4.13–4.294.155.46
PFHxA2080%10.6
2023-04-10
4.37–4.963.568.410
PFBS2050%4.9
2023-04-10
2.1–3.6<MRL4.14.94.9
PFHxS2040%25.8
2023-04-10
5.97–7.78<MRL8.519.224.9
PFOA2040%8.3
2023-04-10
2.29–4.68<MRL4.76.27.9
PFOS2040%7.3
2023-04-10
2.29–4.7<MRL577

Never detected (23): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-16; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build a6f3d99247ed · 2026-10-18T04:13Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.