City Of League City

PFAS monitoring results for a public water system in Texas

TX0840007UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
4.8Highest PFOS result, ppt
0.452Highest Hazard Index
356Results
PWSID
TX0840007
State
Texas
System type
community water system (CWS)
Population served
149,557
City
League City
Counties
Galveston County
Primary source water
surface water (purchased)
UCMR 5 sampling
2024-12-11 to 2026-03-17 · 4 entry point(s) · water types: GW;SW
Service-area boundary
authoritative

PFOS 1–3 × its limit highest single result
PFOS below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)4.82.234
Hazard Index0.4520.1931.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Texas PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; TCEQ implementing federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2024-12-11 to 2026-03-17 · 4 entry point(s) · water types: GW;SW · 15 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-12-11Calder Plant (GW)SE1<4<40lithium 15.5 µg/L
2024-12-11Gulf Coast Water Intertie (SW)SE1n/an/an/alithium 11.3 µg/L
2024-12-11Houston Water Intertie (SW)SE1<44.80.452PFBA 11.2, PFHxA 7.1, PFPeA 7.1
2024-12-11South Shore Harbor Plant (GW)SE1<4<40lithium 13.5 µg/L
2025-01-08Gulf Coast Water Intertie (SW)SE1<4<40.002PFBA 31.9, PFHxA 5.2, PFPeA 102
2025-03-24Gulf Coast Water Intertie (SW)SE2<4<40.002PFBA 14.9, PFHxA 3.6, PFPeA 45.8, lithium 9.5 µg/L
2025-03-24Houston Water Intertie (SW)SE2<4<40.32PFHxA 4.3, PFPeA 4.8
2025-06-24Calder Plant (GW)SE2<4<40PFBA 7.5, PFHxA 3.6, PFPeA 3.8
2025-06-24Gulf Coast Water Intertie (SW)SE3<4<40PFBA 5.7, PFHxA 3.6, PFPeA 3.7
2025-06-24Houston Water Intertie (SW)SE3<4<40PFBA 6.7, PFHxA 3.7, PFPeA 4.1
2025-06-24South Shore Harbor Plant (GW)SE2<4<40PFBA 5.8, PFHxA 3.7, PFPeA 3.6
2025-12-01Gulf Coast Water Intertie (SW)SE4<4<40PFBA 12.1, PFHxA 4.3, PFPeA 24.1, lithium 10 µg/L
2025-12-01Houston Water Intertie (SW)SE4n/an/an/anone
2026-01-26Gulf Coast Water Intertie (SW)SE2n/an/an/anone
2026-03-17Houston Water Intertie (SW)SE4<44.10.002PFBA 5.1, PFHxA 4.7, PFPeA 4.3

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

356 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Calder Plant facility 01621 · sample point EP009 · groundwater

CompoundMRL2024-12-11
SE1
2025-06-24
SE2
PFBA5 ppt< 57.5
PFHxA3 ppt< 33.6
PFPeA3 ppt< 33.8
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L15.5< 9

Gulf Coast Water Intertie facility 64061 · sample point EP003 · surface water

CompoundMRL2024-12-11
SE1
2025-01-08
SE1
2025-03-24
SE2
2025-06-24
SE3
2025-12-01
SE4
2026-01-26
SE2
PFBA5 ppt–31.914.95.712.1–
PFBS3 ppt–4.13.1< 3< 3–
PFHxA3 ppt–5.23.63.64.3–
PFPeA3 ppt–10245.83.724.1–
11Cl-PF3OUdS5 ppt–< 5< 5< 5< 5–
4:2 FTS3 ppt–< 3< 3< 3< 3–
6:2 FTS5 ppt–< 5< 5< 5< 5–
8:2 FTS5 ppt–< 5< 5< 5< 5–
9Cl-PF3ONS2 ppt–< 2< 2< 2< 2–
ADONA3 ppt–< 3< 3< 3< 3–
HFPO-DA5 ppt–< 5< 5< 5< 5–
NEtFOSAA5 ppt< 5––< 5< 5< 5
NFDHA20 ppt–< 20< 20< 20< 20–
NMeFOSAA6 ppt< 6––< 6< 6< 6
PFDA3 ppt–< 3< 3< 3< 3–
PFDoA3 ppt–< 3< 3< 3< 3–
PFEESA3 ppt–< 3< 3< 3< 3–
PFHpA3 ppt–< 3< 3< 3< 3–
PFHpS3 ppt–< 3< 3< 3< 3–
PFHxS3 ppt–< 3< 3< 3< 3–
PFMBA3 ppt–< 3< 3< 3< 3–
PFMPA4 ppt–< 4< 4< 4< 4–
PFNA4 ppt–< 4< 4< 4< 4–
PFOA4 ppt–< 4< 4< 4< 4–
PFOS4 ppt–< 4< 4< 4< 4–
PFPeS4 ppt–< 4< 4< 4< 4–
PFTA8 ppt< 8––< 8< 8< 8
PFTrDA7 ppt< 7––< 7< 7< 7
PFUnA2 ppt–< 2< 2< 2< 2–
lithium9 µg/L11.3–9.5< 910–

Houston Water Intertie facility 06422 · sample point EP001 · surface water

CompoundMRL2024-12-11
SE1
2025-03-24
SE2
2025-06-24
SE3
2025-12-01
SE4
2026-03-17
SE4
PFBA5 ppt11.2< 56.7–5.1
PFBS3 ppt3.7< 3< 3–3.5
PFHxA3 ppt7.14.33.7–4.7
PFHxS3 ppt4.53.2< 3–< 3
PFOS4 ppt4.8< 4< 4–4.1
PFPeA3 ppt7.14.84.1–4.3
11Cl-PF3OUdS5 ppt< 5< 5< 5–< 5
4:2 FTS3 ppt< 3< 3< 3–< 3
6:2 FTS5 ppt< 5< 5< 5–< 5
8:2 FTS5 ppt< 5< 5< 5–< 5
9Cl-PF3ONS2 ppt< 2< 2< 2–< 2
ADONA3 ppt< 3< 3< 3–< 3
HFPO-DA5 ppt< 5< 5< 5–< 5
NEtFOSAA5 ppt< 5–< 5< 5–
NFDHA20 ppt< 20< 20< 20–< 20
NMeFOSAA6 ppt< 6–< 6< 6–
PFDA3 ppt< 3< 3< 3–< 3
PFDoA3 ppt< 3< 3< 3–< 3
PFEESA3 ppt< 3< 3< 3–< 3
PFHpA3 ppt< 3< 3< 3–< 3
PFHpS3 ppt< 3< 3< 3–< 3
PFMBA3 ppt< 3< 3< 3–< 3
PFMPA4 ppt< 4< 4< 4–< 4
PFNA4 ppt< 4< 4< 4–< 4
PFOA4 ppt< 4< 4< 4–< 4
PFPeS4 ppt< 4< 4< 4–< 4
PFTA8 ppt< 8–< 8< 8–
PFTrDA7 ppt< 7–< 7< 7–
PFUnA2 ppt< 2< 2< 2–< 2
lithium9 µg/L< 9< 9< 9< 9–

South Shore Harbor Plant facility 11889 · sample point EP008 · groundwater

CompoundMRL2024-12-11
SE1
2025-06-24
SE2
PFBA5 ppt< 55.8
PFHxA3 ppt< 33.7
PFPeA3 ppt< 33.6
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L13.5< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFHxA1283%7.1
2024-12-11
3.65–4.153.74.35.27.1
PFPeA1283%102
2025-01-08
16.94–17.444.17.145.8102
PFBA1275%31.9
2025-01-08
8.41–9.665.811.214.931.9
lithium1242%15.5
2024-12-11
4.98–10.23<MRL1013.515.5
PFBS1233%4.1
2025-01-08
1.2–3.2<MRL3.13.74.1
PFHxS1217%4.5
2024-12-11
0.64–3.14<MRL<MRL3.24.5
PFOS1217%4.8
2024-12-11
0.74–4.08<MRL<MRL4.14.8

Never detected (23): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFOA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-16; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build a6f3d99247ed · 2026-10-18T04:13Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.