City Of Irving

PFAS monitoring results for a public water system in Texas

TX0570050UCMR 5EPA monitoring data
4.9Highest PFOA result, ppt
4Highest PFOS result, ppt
0.303Highest Hazard Index
360Results
PWSID
TX0570050
State
Texas
System type
community water system (CWS)
Population served
264,546
City
Irving
Counties
Dallas County
Primary source water
surface water (purchased)
UCMR 5 sampling
2023-07-11 to 2024-04-08 · 3 entry point(s) · water types: SW
Service-area boundary
authoritative

PFOA 1–3 × its limit highest single result
PFOA below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

  • Dallas Water Utility (TX0570004)
    Seller's highest results: PFOA 6.3 ppt · PFOS 5.1 ppt · HI 0.384 · detected: PFBA;PFBS;PFHpA;PFHxA;PFHxS;PFOA;PFOS;PFPeA

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)4.92.254
PFOS (ppt)414
Hazard Index0.3030.0771.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Texas PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; TCEQ implementing federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2023-07-11 to 2024-04-08 · 3 entry point(s) · water types: SW · 12 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2023-07-11Hackberry Pump Station (SW)SE1<4<40.002PFBA 8.8, PFHxA 7.1, PFPeA 6.9
2023-07-11Mac Arthur Pump Station (SW)SE14.1<40.003PFBA 8.5, PFHpA 3.2, PFHxA 11.9, PFPeA 11.7
2023-07-11Northgate Pump Station (SW)SE1<4<40.003PFBA 7.9, PFHxA 7.4, PFPeA 7.2
2023-10-18Hackberry Pump Station (SW)SE2<4<40.002PFBA 9.6, PFHxA 6.8, PFPeA 6.9
2023-10-18Mac Arthur Pump Station (SW)SE2<4<40.002PFBA 10, PFHxA 6.8, PFPeA 6.9
2023-10-18Northgate Pump Station (SW)SE2<4<40.002PFBA 10, PFHxA 7.4, PFPeA 7.4
2024-01-29Hackberry Pump Station (SW)SE34<40.003PFBA 11.1, PFHxA 7.9, PFPeA 7.6, lithium 9.99 µg/L
2024-01-29Mac Arthur Pump Station (SW)SE34.940.303PFBA 11.8, PFHpA 3.2, PFHxA 10.2, PFPeA 9.9, lithium 9.67 µg/L
2024-01-29Northgate Pump Station (SW)SE34<40.002PFBA 11.3, PFHxA 8, PFPeA 7.9, lithium 9.05 µg/L
2024-04-08Hackberry Pump Station (SW)SE4<4<40.002PFBA 8.9, PFHxA 6.9, PFPeA 6.7, lithium 9.72 µg/L
2024-04-08Mac Arthur Pump Station (SW)SE4<4<40.002PFBA 9.8, PFHxA 7.1, PFPeA 7.2, lithium 9.07 µg/L
2024-04-08Northgate Pump Station (SW)SE4<4<40.002PFBA 9.4, PFHxA 8.1, PFPeA 7.9

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

360 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Hackberry Pump Station facility 34644 · sample point EP005 · surface water

CompoundMRL2023-07-11
SE1
2023-10-18
SE2
2024-01-29
SE3
2024-04-08
SE4
PFBA5 ppt8.89.611.18.9
PFBS3 ppt4.53.854.4
PFHxA3 ppt7.16.87.96.9
PFOA4 ppt< 4< 44< 4
PFPeA3 ppt6.96.97.66.7
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 99.999.72

Mac Arthur Pump Station facility 34643 · sample point EP001 · surface water

CompoundMRL2023-07-11
SE1
2023-10-18
SE2
2024-01-29
SE3
2024-04-08
SE4
PFBA5 ppt8.51011.89.8
PFBS3 ppt5.345.54.5
PFHpA3 ppt3.2< 33.2< 3
PFHxA3 ppt11.96.810.27.1
PFHxS3 ppt< 3< 33< 3
PFOA4 ppt4.1< 44.9< 4
PFOS4 ppt< 4< 44< 4
PFPeA3 ppt11.76.99.97.2
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 99.679.07

Northgate Pump Station facility 34645 · sample point EP006 · surface water

CompoundMRL2023-07-11
SE1
2023-10-18
SE2
2024-01-29
SE3
2024-04-08
SE4
PFBA5 ppt7.91011.39.4
PFBS3 ppt5.64.24.74.7
PFHxA3 ppt7.47.488.1
PFOA4 ppt< 4< 44< 4
PFPeA3 ppt7.27.47.97.9
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 99.05< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBA12100%11.8
2024-01-29
9.76–9.769.61011.311.8
PFBS12100%5.6
2023-07-11
4.68–4.684.555.55.6
PFHxA12100%11.9
2023-07-11
7.97–7.977.4810.211.9
PFPeA12100%11.7
2023-07-11
7.85–7.857.27.99.911.7
lithium1242%9.99
2024-01-29
3.96–9.21<MRL9.079.729.99
PFOA1233%4.9
2024-01-29
1.42–4.08<MRL44.14.9
PFHpA1217%3.2
2023-07-11
0.53–3.03<MRL<MRL3.23.2
PFHxS128%3
2024-01-29
0.25–3<MRL<MRL<MRL3
PFOS128%4
2024-01-29
0.33–4<MRL<MRL<MRL4

Never detected (21): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-16; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build a6f3d99247ed · 2026-10-18T04:13Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.