- PWSID
- TN0000511
- State
- Tennessee
- System type
- community water system (CWS)
- Population served
- 34,159
- City
- Nolensville
- Counties
- Rutherford County, Williamson County
- Primary source water
- surface water (purchased)
- UCMR 5 sampling
- 2025-03-03 to 2025-12-02 · 3 entry point(s) · water types: SW
- Service-area boundary
- authoritative
PFOA 1–3 × its limit highest single result
PFOA below its limit worst entry-point average
Open on the Tennessee map · All Tennessee systems · All results
These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.
Water purchased from
- Brentwood Water Department (TN0000069)
Seller's highest results: PFOA <MRL · PFOS <MRL · HI 0 - Metro Water Services (TN0000494)
Seller's highest results: PFOA <MRL · PFOS <MRL · HI 0 - Smyrna Water System (TN0000639)
Seller's highest results: PFOA 5.8 ppt · PFOS <MRL · HI 0.011 · detected: PFBA;PFBS;PFHxA;PFOA;PFPeA - Milcrofton Utility District (TN0000247)
Seller's highest results: PFOA <MRL · PFOS <MRL · HI 0 - Mallory Valley U.D. (TN0000428)
Seller's highest results: PFOA <MRL · PFOS <MRL · HI 0
Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.
Compared with EPA's 2024 values
| Highest single result | Worst entry-point average* | Limit | |
|---|---|---|---|
| PFOA (ppt) | 8.1 | 2.02 | 4 |
| PFOS (ppt) | <MRL | 0 | 4 |
| Hazard Index | 0.015 | 0.006 | 1.0† |
“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).
No Tennessee PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; follows federal NPDWR (BCLP state survey, Jan 2026).
Sampling history
Sampled 2025-03-03 to 2025-12-02 · 3 entry point(s) · water types: SW · 13 sampling visits. PFAS in ppt (ng/L).
| Date | Entry point | Event | PFOA | PFOS | HI | Other detections |
|---|---|---|---|---|---|---|
| 2025-03-03 | Mallory Valley Connection (SW) | SE1 | <4 | <4 | 0 | none |
| 2025-03-03 | Metro MM (SW) | SE1 | <4 | <4 | 0 | none |
| 2025-03-03 | Smyrna Connection (SW) | SE1 | <4 | <4 | 0.002 | PFHxA 3.1 |
| 2025-06-02 | Mallory Valley Connection (SW) | SE2 | <4 | <4 | 0 | none |
| 2025-06-02 | Metro MM (SW) | SE2 | <4 | <4 | 0 | none |
| 2025-06-02 | Smyrna Connection (SW) | SE2 | n/a | n/a | n/a | none |
| 2025-06-24 | Smyrna Connection (SW) | SE2 | <4 | <4 | 0.002 | PFHxA 3.9 |
| 2025-09-02 | Mallory Valley Connection (SW) | SE3 | <4 | <4 | 0 | none |
| 2025-09-02 | Metro MM (SW) | SE3 | <4 | <4 | 0 | none |
| 2025-09-02 | Smyrna Connection (SW) | SE3 | 8.1 | <4 | 0.015 | PFBA 11.7, PFHpA 3.1, PFHxA 28.3, PFPeA 14.5 |
| 2025-12-02 | Mallory Valley Connection (SW) | SE4 | <4 | <4 | 0 | none |
| 2025-12-02 | Metro MM (SW) | SE4 | <4 | <4 | 0 | none |
| 2025-12-02 | Smyrna Connection (SW) | SE4 | <4 | <4 | 0.005 | PFHxA 8.7, PFPeA 4.9 |
“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).
All results by entry point
360 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.
Mallory Valley Connection facility 90002 · sample point CC07 · surface water
| Compound | MRL | 2025-03-03 SE1 | 2025-06-02 SE2 | 2025-09-02 SE3 | 2025-12-02 SE4 |
|---|---|---|---|---|---|
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | < 6 | < 6 |
| PFBA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| PFBS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFDA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHpA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHxA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHxS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFOA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFOS | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFPeA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFPeS | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | < 9 | < 9 |
Metro MM facility 90004 · sample point CC09 · surface water
| Compound | MRL | 2025-03-03 SE1 | 2025-06-02 SE2 | 2025-09-02 SE3 | 2025-12-02 SE4 |
|---|---|---|---|---|---|
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | < 6 | < 6 |
| PFBA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| PFBS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFDA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHpA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHxA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHxS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFOA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFOS | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFPeA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFPeS | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | < 9 | < 9 |
Smyrna Connection facility 90001 · sample point CC04 · surface water
| Compound | MRL | 2025-03-03 SE1 | 2025-06-02 SE2 | 2025-06-24 SE2 | 2025-09-02 SE3 | 2025-12-02 SE4 |
|---|---|---|---|---|---|---|
| PFBA | 5 ppt | < 5 | – | < 5 | 11.7 | < 5 |
| PFBS | 3 ppt | 3.8 | – | 4.8 | 30.7 | 10.8 |
| PFHpA | 3 ppt | < 3 | – | < 3 | 3.1 | < 3 |
| PFHxA | 3 ppt | 3.1 | – | 3.9 | 28.3 | 8.7 |
| PFOA | 4 ppt | < 4 | – | < 4 | 8.1 | < 4 |
| PFPeA | 3 ppt | < 3 | – | < 3 | 14.5 | 4.9 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | – | < 5 | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | – | < 5 | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | – | < 5 | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | – | < 2 | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | – | < 5 | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | – | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | – | < 20 | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | – | < 6 | < 6 |
| PFDA | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| PFHxS | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | – | < 3 | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | – | < 4 | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | – | < 4 | < 4 | < 4 |
| PFOS | 4 ppt | < 4 | – | < 4 | < 4 | < 4 |
| PFPeS | 4 ppt | < 4 | – | < 4 | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | – | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 | – | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | – | < 2 | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | – | < 9 | < 9 |
Statistics by compound
| Compound | Results | Detected | Highest (date) | Mean bounds | KM median | P75 | P90 | P95 |
|---|---|---|---|---|---|---|---|---|
| PFBS | 12 | 33% | 30.7 2025-09-02 | 4.17–6.17 | <MRL | 3.8 | 10.8 | 30.7 |
| PFHxA | 12 | 33% | 28.3 2025-09-02 | 3.67–5.67 | <MRL | 3.1 | 8.7 | 28.3 |
| PFPeA | 12 | 17% | 14.5 2025-09-02 | 1.62–4.12 | <MRL | <MRL | 4.9 | 14.5 |
| PFBA | 12 | 8% | 11.7 2025-09-02 | 0.97–5.56 | <MRL | <MRL | <MRL | 11.7 |
| PFHpA | 12 | 8% | 3.1 2025-09-02 | 0.26–3.01 | <MRL | <MRL | <MRL | 3.1 |
| PFOA | 12 | 8% | 8.1 2025-09-02 | 0.68–4.34 | <MRL | <MRL | <MRL | 8.1 |
Never detected (24): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpS, PFHxS, PFMBA, PFMPA, PFNA, PFOS, PFPeS, PFTA, PFTrDA, PFUnA, lithium.
Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.
Sources
- EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-05-12; data summary dated Jul 2026)
- EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
- EPA Public Water System Service Areas v3 (Mar 2026)
- US Census Bureau cartographic boundary counties 1:500k, 2024
- EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+
Data build e2816911520e · 2026-10-18T04:08Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.