PFAS monitoring results for a public water system in Pennsylvania

PA7360128UCMR 5EPA monitoring data
5Highest PFOA result, ppt
4.4Highest PFOS result, ppt
0.002Highest Hazard Index
120Results
PWSID
PA7360128
State
Pennsylvania
System type
community water system (CWS)
Population served
4,200
City
Akron
Counties
Lancaster County
Primary source water
groundwater
UCMR 5 sampling
2023-04-11 to 2023-10-10 · 2 entry point(s) · water types: GW
Service-area boundary
authoritative

PFOA 1–3 × its limit highest single result
PFOA below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

  • Ephrata Area Joint Authority (PA7360045)
    Seller's highest results: PFOA 5.8 ppt · PFOS 4.6 ppt · HI 0.363 · detected: PFBS;PFHxA;PFHxS;PFOA;PFOS;PFPeA

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)52.54
PFOS (ppt)4.42.24
Hazard Index0.0020.0021.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Compared with Pennsylvania standards

Highest single resultWorst entry-point average*Pennsylvania
PFOA (ppt)52.514
PFOS (ppt)4.42.218

Sum standards add the listed compounds within each sample (non-detects = 0). State compliance is normally judged on averages over time; these are screening comparisons.

Sampling history

Sampled 2023-04-11 to 2023-10-10 · 2 entry point(s) · water types: GW · 5 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2023-04-11PUMP HOUSE (GW)SE1n/an/an/anone
2023-04-12EPHRATA INTERCONNECT (GW)SE154.40.002PFHxA 4.4, PFPeA 4.9, lithium 10.5 µg/L
2023-07-26PUMP HOUSE (GW)SE1<4<40PFHpA 4.6, PFHxA 6.2, PFPeA 10.8
2023-10-09PUMP HOUSE (GW)SE2<4<40PFBA 5.4, PFHpA 5.5, PFHxA 7.2, PFPeA 12
2023-10-10EPHRATA INTERCONNECT (GW)SE2<4<40.002PFPeA 3.1

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

120 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

EPHRATA INTERCONNECT facility 102 · sample point EP0001 · groundwater

CompoundMRL2023-04-12
SE1
2023-10-10
SE2
PFBS3 ppt4.83.2
PFHxA3 ppt4.4< 3
PFOA4 ppt5< 4
PFOS4 ppt4.4< 4
PFPeA3 ppt4.93.1
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L10.5< 9

PUMP HOUSE facility 101 · sample point E · groundwater

CompoundMRL2023-04-11
SE1
2023-07-26
SE1
2023-10-09
SE2
PFBA5 ppt–< 55.4
PFHpA3 ppt–4.65.5
PFHxA3 ppt–6.27.2
PFPeA3 ppt–10.812
11Cl-PF3OUdS5 ppt–< 5< 5
4:2 FTS3 ppt–< 3< 3
6:2 FTS5 ppt–< 5< 5
8:2 FTS5 ppt–< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2
ADONA3 ppt–< 3< 3
HFPO-DA5 ppt–< 5< 5
NEtFOSAA5 ppt< 5–< 5
NFDHA20 ppt–< 20< 20
NMeFOSAA6 ppt< 6–< 6
PFBS3 ppt–< 3< 3
PFDA3 ppt–< 3< 3
PFDoA3 ppt–< 3< 3
PFEESA3 ppt–< 3< 3
PFHpS3 ppt–< 3< 3
PFHxS3 ppt–< 3< 3
PFMBA3 ppt–< 3< 3
PFMPA4 ppt–< 4< 4
PFNA4 ppt–< 4< 4
PFOA4 ppt–< 4< 4
PFOS4 ppt–< 4< 4
PFPeS4 ppt–< 4< 4
PFTA8 ppt< 8–< 8
PFTrDA7 ppt< 7–< 7
PFUnA2 ppt–< 2< 2
lithium9 µg/L< 9–< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFPeA4100%12
2023-10-09
7.7–7.74.910.81212
PFHxA475%7.2
2023-10-09
4.45–5.24.46.27.27.2
PFBS450%4.8
2023-04-12
2–3.5<MRL3.24.84.8
PFHpA450%5.5
2023-10-09
2.52–4.03<MRL4.65.55.5
PFBA425%5.4
2023-10-09
1.35–5.1<MRL<MRL5.45.4
PFOA425%5
2023-04-12
1.25–4.25<MRL<MRL55
PFOS425%4.4
2023-04-12
1.1–4.1<MRL<MRL4.44.4
lithium425%10.5
2023-04-12
2.62–9.38<MRL<MRL10.510.5

Never detected (22): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpS, PFHxS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-10 to 2026-04-09; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 52bd2907cbc3 · 2026-10-18T04:10Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.