Cincinnati Childrens Hosp Ionization Sys

PFAS monitoring results for a public water system in Ohio

OH3139912UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
<MRLHighest PFOS result, ppt
0.63Highest Hazard Index
360Results
PWSID
OH3139912
State
Ohio
System type
non-transient non-community water system (NTNCWS)
Population served
1,514
City
Cincinnati
Counties
Hamilton County
Primary source water
surface water (purchased)
UCMR 5 sampling
2024-03-13 to 2024-12-11 · 3 entry point(s) · water types: SW
Service-area boundary
parcel-based (EPA non-community layer)

Hazard Index below its limit highest single result
Hazard Index below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)<MRL04
Hazard Index0.630.1581.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Ohio PFAS drinking-water standard in effect or proposed as of 2026-10-17: No Ohio-specific PFAS drinking-water MCL; Ohio EPA follows federal values.

Sampling history

Sampled 2024-03-13 to 2024-12-11 · 3 entry point(s) · water types: SW · 13 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-03-13CCHMC Main Campus LOC A (SW)SE1n/an/an/anone
2024-03-13CCHMC Main Campus LOC B (SW)SE1<4<40none
2024-03-13CCHMC Main Campus LOC G (SW)SE1<4<40none
2024-04-24CCHMC Main Campus LOC A (SW)SE1<4<40none
2024-06-10CCHMC Main Campus LOC A (SW)SE2<4<40none
2024-06-10CCHMC Main Campus LOC B (SW)SE2<4<40none
2024-06-10CCHMC Main Campus LOC G (SW)SE2<4<40none
2024-09-23CCHMC Main Campus LOC A (SW)SE3<4<40PFPeA 3.6, lithium 11.9 µg/L
2024-09-23CCHMC Main Campus LOC B (SW)SE3<4<40PFPeA 3.8, lithium 10.2 µg/L
2024-09-23CCHMC Main Campus LOC G (SW)SE3<4<40PFPeA 3.7, lithium 13.5 µg/L
2024-12-11CCHMC Main Campus LOC A (SW)SE4<4<40.61PFPeA 10.8
2024-12-11CCHMC Main Campus LOC B (SW)SE4<4<40.62PFPeA 11.2
2024-12-11CCHMC Main Campus LOC G (SW)SE4<4<40.63PFPeA 10.1

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

360 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

CCHMC Main Campus LOC A facility 3162418 · sample point EP002 · surface water

CompoundMRL2024-03-13
SE1
2024-04-24
SE1
2024-06-10
SE2
2024-09-23
SE3
2024-12-11
SE4
HFPO-DA5 ppt–< 5< 5< 56.1
PFPeA3 ppt–< 3< 33.610.8
11Cl-PF3OUdS5 ppt–< 5< 5< 5< 5
4:2 FTS3 ppt–< 3< 3< 3< 3
6:2 FTS5 ppt–< 5< 5< 5< 5
8:2 FTS5 ppt–< 5< 5< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2< 2< 2
ADONA3 ppt–< 3< 3< 3< 3
NEtFOSAA5 ppt< 5–< 5< 5< 5
NFDHA20 ppt–< 20< 20< 20< 20
NMeFOSAA6 ppt< 6–< 6< 6< 6
PFBA5 ppt–< 5< 5< 5< 5
PFBS3 ppt–< 3< 3< 3< 3
PFDA3 ppt–< 3< 3< 3< 3
PFDoA3 ppt–< 3< 3< 3< 3
PFEESA3 ppt–< 3< 3< 3< 3
PFHpA3 ppt–< 3< 3< 3< 3
PFHpS3 ppt–< 3< 3< 3< 3
PFHxA3 ppt–< 3< 3< 3< 3
PFHxS3 ppt–< 3< 3< 3< 3
PFMBA3 ppt–< 3< 3< 3< 3
PFMPA4 ppt–< 4< 4< 4< 4
PFNA4 ppt–< 4< 4< 4< 4
PFOA4 ppt–< 4< 4< 4< 4
PFOS4 ppt–< 4< 4< 4< 4
PFPeS4 ppt–< 4< 4< 4< 4
PFTA8 ppt< 8–< 8< 8< 8
PFTrDA7 ppt< 7–< 7< 7< 7
PFUnA2 ppt–< 2< 2< 2< 2
lithium9 µg/L< 9–< 911.9< 9

CCHMC Main Campus LOC B facility 3162419 · sample point EP003 · surface water

CompoundMRL2024-03-13
SE1
2024-06-10
SE2
2024-09-23
SE3
2024-12-11
SE4
HFPO-DA5 ppt< 5< 5< 56.2
PFPeA3 ppt< 3< 33.811.2
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFBA5 ppt< 5< 5< 5< 5
PFBS3 ppt< 3< 3< 3< 3
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxA3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 910.2< 9

CCHMC Main Campus LOC G facility 3162411 · sample point EP001 · surface water

CompoundMRL2024-03-13
SE1
2024-06-10
SE2
2024-09-23
SE3
2024-12-11
SE4
HFPO-DA5 ppt< 5< 5< 56.3
PFPeA3 ppt< 3< 33.710.1
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFBA5 ppt< 5< 5< 5< 5
PFBS3 ppt< 3< 3< 3< 3
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxA3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 913.5< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFPeA1250%11.2
2024-12-11
3.6–5.1<MRL3.810.811.2
HFPO-DA1225%6.3
2024-12-11
1.55–5.3<MRL<MRL6.26.3
lithium1225%13.5
2024-09-23
2.97–9.72<MRL<MRL11.913.5

Never detected (27): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFHxA, PFHxS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-03-31; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 9d02e90cf16d · 2026-10-18T04:07Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.