Willingboro Mua

PFAS monitoring results for a public water system in New Jersey

NJ0338001UCMR 5EPA monitoring data
10.6Highest PFOA result, ppt
10.6Highest PFOS result, ppt
0.65Highest Hazard Index
240Results
PWSID
NJ0338001
State
New Jersey
System type
community water system (CWS)
Population served
35,000
City
Willingbor0
Counties
Burlington County
Primary source water
groundwater
UCMR 5 sampling
2024-06-13 to 2024-12-10 · 4 entry point(s) · water types: GW
Service-area boundary
authoritative

PFOA 1–3 × its limit highest single result
PFOS 1–3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)10.69.654
PFOS (ppt)10.6104
Hazard Index0.650.6151.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Compared with New Jersey standards

Highest single resultWorst entry-point average*New Jersey
PFNA (ppt)0013
PFOA (ppt)10.69.6514
PFOS (ppt)10.61013

Sum standards add the listed compounds within each sample (non-detects = 0). State compliance is normally judged on averages over time; these are screening comparisons.

Sampling history

Sampled 2024-06-13 to 2024-12-10 · 4 entry point(s) · water types: GW · 8 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-06-13Baldwin Lane TP (GW)SE1<4<40lithium 29.9 µg/L
2024-06-13Medallion Lane TP (GW)SE1<4<40lithium 12.6 µg/L
2024-06-13Meribrook TP (GW)SE1<49.40.58lithium 21.8 µg/L
2024-06-13Sylvan Lane TP (GW)SE18.74.10.36PFHxA 3.5, PFPeA 3.3, lithium 24.2 µg/L
2024-12-10Baldwin Lane TP (GW)SE2<4<40lithium 29.9 µg/L
2024-12-10Medallion Lane TP (GW)SE2<4<40lithium 11.3 µg/L
2024-12-10Meribrook TP (GW)SE2<410.60.65lithium 21 µg/L
2024-12-10Sylvan Lane TP (GW)SE210.65.20.41PFHxA 4.3, PFPeA 4.4, lithium 22.9 µg/L

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

240 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Baldwin Lane TP facility 97018 · sample point TP007018 · groundwater

CompoundMRL2024-06-13
SE1
2024-12-10
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L29.929.9

Medallion Lane TP facility 93010 · sample point TP003010 · groundwater

CompoundMRL2024-06-13
SE1
2024-12-10
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L12.611.3

Meribrook TP facility 91002 · sample point TP001002 · groundwater

CompoundMRL2024-06-13
SE1
2024-12-10
SE2
PFHxS3 ppt5.86.5
PFOS4 ppt9.410.6
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L21.821

Sylvan Lane TP facility 92006 · sample point TP002006 · groundwater

CompoundMRL2024-06-13
SE1
2024-12-10
SE2
PFHxA3 ppt3.54.3
PFHxS3 ppt3.64.1
PFOA4 ppt8.710.6
PFOS4 ppt4.15.2
PFPeA3 ppt3.34.4
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L24.222.9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
lithium8100%29.9
2024-06-13
21.7–21.721.824.229.929.9
PFHxS850%6.5
2024-12-10
2.5–4<MRL4.16.56.5
PFOS850%10.6
2024-12-10
3.66–5.66<MRL5.210.610.6
PFHxA825%4.3
2024-12-10
0.97–3.23<MRL<MRL4.34.3
PFOA825%10.6
2024-12-10
2.41–5.41<MRL<MRL10.610.6
PFPeA825%4.4
2024-12-10
0.96–3.21<MRL<MRL4.44.4

Never detected (24): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-05-29; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 0c4398dd12d6 · 2026-10-18T04:09Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.