- PWSID
- NC0326010
- State
- North Carolina
- System type
- community water system (CWS)
- Population served
- 226,441
- City
- Fayetteville
- Counties
- Cumberland County
- Primary source water
- surface water
- UCMR 5 sampling
- 2023-10-17 to 2024-07-10 · 2 entry point(s) · water types: SW
- Service-area boundary
- authoritative
PFOS ≥ 3 × its limit highest single result
PFOS ≥ 3 × its limit worst entry-point average
Open on the North Carolina map · All North Carolina systems · All results
These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.
Compared with EPA's 2024 values
| Highest single result | Worst entry-point average* | Limit | |
|---|---|---|---|
| PFOA (ppt) | 11 | 8.45 | 4 |
| PFOS (ppt) | 21.8 | 16.85 | 4 |
| Hazard Index | 1.913 | 1.134 | 1.0† |
“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).
No North Carolina PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water MCL in effect; S.B. 384 (2025) filed, not enacted; DEQ implementing federal NPDWR.
Sampling history
Sampled 2023-10-17 to 2024-07-10 · 2 entry point(s) · water types: SW · 8 sampling visits. PFAS in ppt (ng/L).
| Date | Entry point | Event | PFOA | PFOS | HI | Other detections |
|---|---|---|---|---|---|---|
| 2023-10-17 | Glenville WTP (SW) | SE1 | 11 | 16.3 | 0.826 | 6:2 FTS 7.7, PFBA 11.4, PFHpA 7, PFHxA 18.2, PFPeA 21.5 |
| 2023-10-17 | Hoffer WTP (SW) | SE1 | 8.6 | 21.8 | 1.913 | PFHxA 6.4, PFPeA 5.1 |
| 2024-01-10 | Glenville WTP (SW) | SE2 | 6.3 | 15.6 | 1.433 | PFHxA 4.5, PFPeA 3.2 |
| 2024-01-10 | Hoffer WTP (SW) | SE2 | 7 | 11.2 | 0.372 | PFBA 5.2, PFHpA 3.2, PFHxA 6.5, PFPeA 5.5 |
| 2024-04-02 | Glenville WTP (SW) | SE3 | 7.4 | 20.1 | 1.663 | PFHxA 5.3, PFPeA 3.7 |
| 2024-04-02 | Hoffer WTP (SW) | SE3 | 8.1 | 12.3 | 0.322 | PFHpA 3, PFHxA 5.5, PFPeA 4.3 |
| 2024-07-10 | Glenville WTP (SW) | SE4 | 9.1 | 15.4 | 0.614 | PFBA 7.9, PFHpA 4.4, PFHxA 11.1, PFPeA 11.3 |
| 2024-07-10 | Hoffer WTP (SW) | SE4 | 8.5 | 13.3 | 0.464 | PFBA 7.9, PFHpA 4.3, PFHxA 11.1, PFPeA 11.2 |
“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).
All results by entry point
240 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.
Glenville WTP facility 00011 · sample point EP2 · surface water
| Compound | MRL | 2023-10-17 SE1 | 2024-01-10 SE2 | 2024-04-02 SE3 | 2024-07-10 SE4 |
|---|---|---|---|---|---|
| 6:2 FTS | 5 ppt | 7.7 | < 5 | < 5 | < 5 |
| PFBA | 5 ppt | 11.4 | < 5 | < 5 | 7.9 |
| PFBS | 3 ppt | 12.1 | 5.1 | 6.2 | 7.5 |
| PFHpA | 3 ppt | 7 | < 3 | < 3 | 4.4 |
| PFHxA | 3 ppt | 18.2 | 4.5 | 5.3 | 11.1 |
| PFHxS | 3 ppt | 8.2 | 14.3 | 16.6 | 6.1 |
| PFOA | 4 ppt | 11 | 6.3 | 7.4 | 9.1 |
| PFOS | 4 ppt | 16.3 | 15.6 | 20.1 | 15.4 |
| PFPeA | 3 ppt | 21.5 | 3.2 | 3.7 | 11.3 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| 8:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | < 6 | < 6 |
| PFDA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFPeS | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | < 9 | < 9 |
Hoffer WTP facility 00010 · sample point EP1 · surface water
| Compound | MRL | 2023-10-17 SE1 | 2024-01-10 SE2 | 2024-04-02 SE3 | 2024-07-10 SE4 |
|---|---|---|---|---|---|
| PFBA | 5 ppt | < 5 | 5.2 | < 5 | 7.9 |
| PFBS | 3 ppt | 6.9 | 4.5 | 3.6 | 7 |
| PFHpA | 3 ppt | < 3 | 3.2 | 3 | 4.3 |
| PFHxA | 3 ppt | 6.4 | 6.5 | 5.5 | 11.1 |
| PFHxS | 3 ppt | 19.1 | 3.7 | 3.2 | 4.6 |
| PFOA | 4 ppt | 8.6 | 7 | 8.1 | 8.5 |
| PFOS | 4 ppt | 21.8 | 11.2 | 12.3 | 13.3 |
| PFPeA | 3 ppt | 5.1 | 5.5 | 4.3 | 11.2 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | < 5 | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | < 6 | < 6 |
| PFDA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFPeS | 4 ppt | < 4 | < 4 | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | < 8 | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 | < 7 | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | < 9 | < 9 |
Statistics by compound
| Compound | Results | Detected | Highest (date) | Mean bounds | KM median | P75 | P90 | P95 |
|---|---|---|---|---|---|---|---|---|
| PFBS | 8 | 100% | 12.1 2023-10-17 | 6.61–6.61 | 6.2 | 7 | 12.1 | 12.1 |
| PFHxA | 8 | 100% | 18.2 2023-10-17 | 8.57–8.57 | 6.4 | 11.1 | 18.2 | 18.2 |
| PFHxS | 8 | 100% | 19.1 2023-10-17 | 9.47–9.47 | 6.1 | 14.3 | 19.1 | 19.1 |
| PFOA | 8 | 100% | 11 2023-10-17 | 8.25–8.25 | 8.1 | 8.6 | 11 | 11 |
| PFOS | 8 | 100% | 21.8 2023-10-17 | 15.75–15.75 | 15.4 | 16.3 | 21.8 | 21.8 |
| PFPeA | 8 | 100% | 21.5 2023-10-17 | 8.22–8.22 | 5.1 | 11.2 | 21.5 | 21.5 |
| PFHpA | 8 | 62% | 7 2023-10-17 | 2.74–3.86 | 3 | 4.3 | 7 | 7 |
| PFBA | 8 | 50% | 11.4 2023-10-17 | 4.05–6.55 | <MRL | 7.9 | 11.4 | 11.4 |
| 6:2 FTS | 8 | 12% | 7.7 2023-10-17 | 0.96–5.34 | <MRL | <MRL | 7.7 | 7.7 |
Never detected (21): 11Cl-PF3OUdS, 4:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.
Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.
Sources
- EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-03; data summary dated Jul 2026)
- EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
- EPA Public Water System Service Areas v3 (Mar 2026)
- US Census Bureau cartographic boundary counties 1:500k, 2024
- EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+
Data build 06b855374275 · 2026-10-18T04:10Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.