City Of Ridgeland

PFAS monitoring results for a public water system in Mississippi

MS0450013UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
<MRLHighest PFOS result, ppt
0Highest Hazard Index
250Results
PWSID
MS0450013
State
Mississippi
System type
community water system (CWS)
Population served
24,340
City
Ridgeland
Counties
Madison County
Primary source water
groundwater
UCMR 5 sampling
2024-05-28 to 2024-12-17 · 8 entry point(s) · water types: GW
Service-area boundary
authoritative

No PFAS detected highest single result
No PFAS detected worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)<MRL04
Hazard Index001.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Mississippi PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; follows federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2024-05-28 to 2024-12-17 · 8 entry point(s) · water types: GW · 15 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-05-28Charity Church Treatment Facility (GW)SE1<4<40lithium 28.6 µg/L
2024-05-28Hardy St. Treatment Facility (GW)SE1<4<40none
2024-05-28Lake Harbour Dr Treatment Facility (GW)SE1<4<40lithium 17.2 µg/L
2024-05-28Livingston at Walter Peyton TF (GW)SE1<4<40none
2024-05-28Old Canton Road Treatment Facility (GW)SE1<4<40lithium 25.8 µg/L
2024-05-28Peach Orchard Road Treatment Facility (GW)SE1<4<40none
2024-05-28Samuels Lane TF (GW)SE1<4<40none
2024-12-17Charity Church Treatment Facility (GW)SE2n/an/an/alithium 28.7 µg/L
2024-12-17Hardy St. Treatment Facility (GW)SE2n/an/an/anone
2024-12-17Lake Harbour Dr Treatment Facility (GW)SE2n/an/an/alithium 17.7 µg/L
2024-12-17Livingston at Walter Peyton TF (GW)SE2n/an/an/anone
2024-12-17Old Canton Road Treatment Facility (GW)SE2n/an/an/alithium 27.3 µg/L
2024-12-17Peach Orchard Road Treatment Facility (GW)SE2n/an/an/anone
2024-12-17Samuels Lane TF (GW)SE2n/an/an/anone
2024-12-17W. School St. Treatment Facility (GW)SE2n/an/an/anone

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

250 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Charity Church Treatment Facility facility 32720 · sample point 32720 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L28.628.7

Hardy St. Treatment Facility facility 32723 · sample point 32723 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L< 9< 9

Lake Harbour Dr Treatment Facility facility 32721 · sample point 32721 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L17.217.7

Livingston at Walter Peyton TF facility 40001 · sample point 40001 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L< 9< 9

Old Canton Road Treatment Facility facility 33611 · sample point 33611 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L25.827.3

Peach Orchard Road Treatment Facility facility 32719 · sample point 32719 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L< 9< 9

Samuels Lane TF facility 42817 · sample point 42817 · groundwater

CompoundMRL2024-05-28
SE1
2024-12-17
SE2
11Cl-PF3OUdS5 ppt< 5–
4:2 FTS3 ppt< 3–
6:2 FTS5 ppt< 5–
8:2 FTS5 ppt< 5–
9Cl-PF3ONS2 ppt< 2–
ADONA3 ppt< 3–
HFPO-DA5 ppt< 5–
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20–
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5–
PFBS3 ppt< 3–
PFDA3 ppt< 3–
PFDoA3 ppt< 3–
PFEESA3 ppt< 3–
PFHpA3 ppt< 3–
PFHpS3 ppt< 3–
PFHxA3 ppt< 3–
PFHxS3 ppt< 3–
PFMBA3 ppt< 3–
PFMPA4 ppt< 4–
PFNA4 ppt< 4–
PFOA4 ppt< 4–
PFOS4 ppt< 4–
PFPeA3 ppt< 3–
PFPeS4 ppt< 4–
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2–
lithium9 µg/L< 9< 9

W. School St. Treatment Facility facility 32722 · sample point 32722 · groundwater

CompoundMRL2024-12-17
SE2
NEtFOSAA5 ppt< 5
NMeFOSAA6 ppt< 6
PFTA8 ppt< 8
PFTrDA7 ppt< 7
lithium9 µg/L< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
lithium1540%28.7
2024-12-17
9.69–15.09<MRL25.828.628.7

Never detected (29): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFHxA, PFHxS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-23 to 2026-03-18; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 159b8c2ccdd2 · 2026-10-18T04:08Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.