South Lyon, City Of

PFAS monitoring results for a public water system in Michigan

MI0006110UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
<MRLHighest PFOS result, ppt
0.54Highest Hazard Index
60Results
PWSID
MI0006110
State
Michigan
System type
community water system (CWS)
Population served
11,055
City
South Lyon,
Counties
Livingston County, Oakland County
Primary source water
groundwater
UCMR 5 sampling
2024-08-29 to 2025-02-24 · 1 entry point(s) · water types: GW
Service-area boundary
EPA-modeled (Random Forest) — approximate: estimated by EPA with a statistical model, not a surveyed service area

Hazard Index below its limit highest single result
Hazard Index below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)<MRL04
Hazard Index0.540.271.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Compared with Michigan standards

Highest single resultWorst entry-point average*Michigan
PFNA (ppt)006
PFOA (ppt)008
PFOS (ppt)0016
PFHxS (ppt)0051
HFPO-DA (GenX) (ppt)5.42.7370
PFBS (ppt)00420
PFHxA (ppt)00400,000

Sum standards add the listed compounds within each sample (non-detects = 0). State compliance is normally judged on averages over time; these are screening comparisons.

Sampling history

Sampled 2024-08-29 to 2025-02-24 · 1 entry point(s) · water types: GW · 2 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-08-29City of South Lyon Water Treatment Plant (GW)SE1<4<40lithium 9.98 µg/L
2025-02-24City of South Lyon Water Treatment Plant (GW)SE2<4<40.54none

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

60 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

City of South Lyon Water Treatment Plant facility MI0006110 · sample point 1 · groundwater

CompoundMRL2024-08-29
SE1
2025-02-24
SE2
HFPO-DA5 ppt< 55.4
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L9.98< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
HFPO-DA250%5.4
2025-02-24
2.7–5.2fewer than 4 results: raw values only
lithium250%9.98
2024-08-29
4.99–9.49fewer than 4 results: raw values only

Never detected (28): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFHxA, PFHxS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-04 to 2026-01-12; data summary dated Jul 2026)