Independence Township

PFAS monitoring results for a public water system in Michigan

MI0003342UCMR 5EPA monitoring data
7.1Highest PFOA result, ppt
10Highest PFOS result, ppt
3.003Highest Hazard Index
360Results
PWSID
MI0003342
State
Michigan
System type
community water system (CWS)
Population served
11,790
City
Clarkston
Counties
Oakland County
Primary source water
groundwater
UCMR 5 sampling
2024-09-17 to 2025-03-12 · 6 entry point(s) · water types: GW
Service-area boundary
authoritative

Hazard Index ≥ 3 × its limit highest single result
Hazard Index 1–3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)7.15.954
PFOS (ppt)109.74
Hazard Index3.0032.8031.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Compared with Michigan standards

Highest single resultWorst entry-point average*Michigan
PFNA (ppt)006
PFOA (ppt)7.15.958
PFOS (ppt)109.716
PFHxS (ppt)302851
HFPO-DA (GenX) (ppt)00370
PFBS (ppt)6.75.7420
PFHxA (ppt)5.74.5400,000

Sum standards add the listed compounds within each sample (non-detects = 0). State compliance is normally judged on averages over time; these are screening comparisons.

Sampling history

Sampled 2024-09-17 to 2025-03-12 · 6 entry point(s) · water types: GW · 12 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-09-17Bay Court Treatment Plant (GW)SE1<4<40none
2024-09-17Chestnut Hills Treatment Plant (GW)SE1<4<40.003none
2024-09-17Clarkston Gardens Treatment Plant (GW)SE17.1103.003PFBA 5.6, PFHxA 5.7, PFPeA 5.9, PFPeS 5.2
2024-09-17Lake Oakland Woods Treatment Plant (GW)SE1<4<40none
2024-09-17Pelton Heights Treatment Plant (GW)SE1<4<40lithium 10 µg/L
2024-09-17Waldon Creek Treatment Plant (GW)SE1<4<40none
2025-03-12Bay Court Treatment Plant (GW)SE2<4<40none
2025-03-12Chestnut Hills Treatment Plant (GW)SE2<4<40.003none
2025-03-12Clarkston Gardens Treatment Plant (GW)SE24.89.42.602PFHxA 3.3, PFPeA 3.5, PFPeS 4.5
2025-03-12Lake Oakland Woods Treatment Plant (GW)SE2<4<40none
2025-03-12Pelton Heights Treatment Plant (GW)SE2<4<40lithium 11 µg/L
2025-03-12Waldon Creek Treatment Plant (GW)SE2<4<40none

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

360 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Bay Court Treatment Plant facility 09750 · sample point TP104 · groundwater

CompoundMRL2024-09-17
SE1
2025-03-12
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Chestnut Hills Treatment Plant facility 09745 · sample point TP100 · groundwater

CompoundMRL2024-09-17
SE1
2025-03-12
SE2
PFBS3 ppt5.55.2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Clarkston Gardens Treatment Plant facility 09748 · sample point TP101 · groundwater

CompoundMRL2024-09-17
SE1
2025-03-12
SE2
PFBA5 ppt5.6< 5
PFBS3 ppt6.74.7
PFHxA3 ppt5.73.3
PFHxS3 ppt3026
PFOA4 ppt7.14.8
PFOS4 ppt109.4
PFPeA3 ppt5.93.5
PFPeS4 ppt5.24.5
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Lake Oakland Woods Treatment Plant facility 09752 · sample point TP103 · groundwater

CompoundMRL2024-09-17
SE1
2025-03-12
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Pelton Heights Treatment Plant facility 09749 · sample point TP102 · groundwater

CompoundMRL2024-09-17
SE1
2025-03-12
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L1011

Waldon Creek Treatment Plant facility 09753 · sample point TP105 · groundwater

CompoundMRL2024-09-17
SE1
2025-03-12
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBS1233%6.7
2024-09-17
1.84–3.84<MRL4.75.56.7
PFHxA1217%5.7
2024-09-17
0.75–3.25<MRL<MRL3.35.7
PFHxS1217%30
2024-09-17
4.67–7.17<MRL<MRL2630
PFOA1217%7.1
2024-09-17
0.99–4.33<MRL<MRL4.87.1
PFOS1217%10
2024-09-17
1.62–4.95<MRL<MRL9.410
PFPeA1217%5.9
2024-09-17
0.78–3.28<MRL<MRL3.55.9
PFPeS1217%5.2
2024-09-17
0.81–4.14<MRL<MRL4.55.2
lithium1217%11
2025-03-12
1.75–9.25<MRL<MRL1011
PFBA128%5.6
2024-09-17
0.47–5.05<MRL<MRL<MRL5.6

Never detected (21): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-04 to 2026-01-12; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 78395147edcc · 2026-10-18T04:08Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.