Town Of Vidalia Water System

PFAS monitoring results for a public water system in Louisiana

LA1029011UCMR 5EPA monitoring data
20.1Highest PFOA result, ppt
8.5Highest PFOS result, ppt
0.532Highest Hazard Index
60Results
PWSID
LA1029011
State
Louisiana
System type
community water system (CWS)
Population served
6,354
City
Vidalia
Counties
Concordia Parish
Primary source water
groundwater
UCMR 5 sampling
2025-06-02 to 2025-12-02 · 1 entry point(s) · water types: GW
Service-area boundary
EPA-modeled (Random Forest) — approximate: estimated by EPA with a statistical model, not a surveyed service area

PFOA ≥ 3 × its limit highest single result
PFOA ≥ 3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)20.118.954
PFOS (ppt)8.57.94
Hazard Index0.5320.5071.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Louisiana PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; follows federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2025-06-02 to 2025-12-02 · 1 entry point(s) · water types: GW · 2 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2025-06-02CITY OF VIDALIA WATER SYSTEM (GW)SE120.17.30.482PFBA 31.7, PFHpA 3.2, PFHxA 10.8, PFPeA 12.9, lithium 20.9 µg/L
2025-12-02CITY OF VIDALIA WATER SYSTEM (GW)SE217.88.50.532PFBA 30.5, PFHpA 3, PFHxA 10.2, PFPeA 11.5, lithium 17.7 µg/L

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

60 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

CITY OF VIDALIA WATER SYSTEM facility TP004 · sample point 6BBV · groundwater

CompoundMRL2025-06-02
SE1
2025-12-02
SE2
PFBA5 ppt31.730.5
PFBS3 ppt3.53.6
PFHpA3 ppt3.23
PFHxA3 ppt10.810.2
PFNA4 ppt4.85.3
PFOA4 ppt20.117.8
PFOS4 ppt7.38.5
PFPeA3 ppt12.911.5
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L20.917.7

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBA2100%31.7
2025-06-02
31.1–31.1fewer than 4 results: raw values only
PFBS2100%3.6
2025-12-02
3.55–3.55fewer than 4 results: raw values only
PFHpA2100%3.2
2025-06-02
3.1–3.1fewer than 4 results: raw values only
PFHxA2100%10.8
2025-06-02
10.5–10.5fewer than 4 results: raw values only
PFNA2100%5.3
2025-12-02
5.05–5.05fewer than 4 results: raw values only
PFOA2100%20.1
2025-06-02
18.95–18.95fewer than 4 results: raw values only
PFOS2100%8.5
2025-12-02
7.9–7.9fewer than 4 results: raw values only
PFPeA2100%12.9
2025-06-02
12.2–12.2fewer than 4 results: raw values only
lithium2100%20.9
2025-06-02
19.3–19.3fewer than 4 results: raw values only

Never detected (21): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpS, PFHxS, PFMBA, PFMPA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-05-12; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 6e7fb171ec63 · 2026-10-18T04:08Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.