Parish Utilities Of Ascension

PFAS monitoring results for a public water system in Louisiana

LA1005035UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
4.5Highest PFOS result, ppt
0.002Highest Hazard Index
120Results
PWSID
LA1005035
State
Louisiana
System type
community water system (CWS)
Population served
9,732
City
Donaldsonville
Counties
Ascension Parish
Primary source water
surface water
UCMR 5 sampling
2023-01-09 to 2024-01-17 · 1 entry point(s) · water types: SW
Service-area boundary
EPA-modeled (Random Forest) — approximate: estimated by EPA with a statistical model, not a surveyed service area

PFOS 1–3 × its limit highest single result
PFOS below its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)4.51.124
Hazard Index0.0020.0011.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Louisiana PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water standard; follows federal NPDWR (BCLP state survey, Jan 2026).

Sampling history

Sampled 2023-01-09 to 2024-01-17 · 1 entry point(s) · water types: SW · 8 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2023-01-09PARISH UTILITIES OF ASCENSION (SW)SE1<4<40.002PFBA 6.6
2023-04-05PARISH UTILITIES OF ASCENSION (SW)SE2<4<40PFBA 6.3
2023-06-20PARISH UTILITIES OF ASCENSION (SW)SE2n/an/an/anone
2023-07-11PARISH UTILITIES OF ASCENSION (SW)SE3n/an/an/alithium 10.4 µg/L
2023-08-01PARISH UTILITIES OF ASCENSION (SW)SE3n/an/an/anone
2023-08-30PARISH UTILITIES OF ASCENSION (SW)SE3<44.50PFBA 6.7
2023-10-03PARISH UTILITIES OF ASCENSION (SW)SE4n/an/an/alithium 13.1 µg/L
2024-01-17PARISH UTILITIES OF ASCENSION (SW)SE4<4<40PFBA 5

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

120 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

PARISH UTILITIES OF ASCENSION facility TP001 · sample point 2AJU · surface water

CompoundMRL2023-01-09
SE1
2023-04-05
SE2
2023-06-20
SE2
2023-07-11
SE3
2023-08-01
SE3
2023-08-30
SE3
2023-10-03
SE4
2024-01-17
SE4
PFBA5 ppt6.66.3–––6.7–5
PFBS3 ppt4.7< 3–––< 3–< 3
PFOS4 ppt< 4< 4–––4.5–< 4
11Cl-PF3OUdS5 ppt< 5< 5–––< 5–< 5
4:2 FTS3 ppt< 3< 3–––< 3–< 3
6:2 FTS5 ppt< 5< 5–––< 5–< 5
8:2 FTS5 ppt< 5< 5–––< 5–< 5
9Cl-PF3ONS2 ppt< 2< 2–––< 2–< 2
ADONA3 ppt< 3< 3–––< 3–< 3
HFPO-DA5 ppt< 5< 5–––< 5–< 5
NEtFOSAA5 ppt< 5–< 5–< 5––< 5
NFDHA20 ppt< 20< 20–––< 20–< 20
NMeFOSAA6 ppt< 6–< 6–< 6––< 6
PFDA3 ppt< 3< 3–––< 3–< 3
PFDoA3 ppt< 3< 3–––< 3–< 3
PFEESA3 ppt< 3< 3–––< 3–< 3
PFHpA3 ppt< 3< 3–––< 3–< 3
PFHpS3 ppt< 3< 3–––< 3–< 3
PFHxA3 ppt< 3< 3–––< 3–< 3
PFHxS3 ppt< 3< 3–––< 3–< 3
PFMBA3 ppt< 3< 3–––< 3–< 3
PFMPA4 ppt< 4< 4–––< 4–< 4
PFNA4 ppt< 4< 4–––< 4–< 4
PFOA4 ppt< 4< 4–––< 4–< 4
PFPeA3 ppt< 3< 3–––< 3–< 3
PFPeS4 ppt< 4< 4–––< 4–< 4
PFTA8 ppt< 8–< 8–< 8––< 8
PFTrDA7 ppt< 7–< 7–< 7––< 7
PFUnA2 ppt< 2< 2–––< 2–< 2
lithium9 µg/L< 9< 9–10.4––13.1–

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBA4100%6.7
2023-08-30
6.15–6.156.36.66.76.7
lithium450%13.1
2023-10-03
5.88–10.38<MRL10.413.113.1
PFBS425%4.7
2023-01-09
1.18–3.42<MRL<MRL4.74.7
PFOS425%4.5
2023-08-30
1.12–4.12<MRL<MRL4.54.5

Never detected (26): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFHxA, PFHxS, PFMBA, PFMPA, PFNA, PFOA, PFPeA, PFPeS, PFTA, PFTrDA, PFUnA.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-05-12; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 6e7fb171ec63 · 2026-10-18T04:08Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.