Floyd County

PFAS monitoring results for a public water system in Georgia

GA1150001UCMR 5EPA monitoring data
13.6Highest PFOA result, ppt
9.2Highest PFOS result, ppt
0.047Highest Hazard Index
540Results
PWSID
GA1150001
State
Georgia
System type
community water system (CWS)
Population served
46,143
City
Rome
Counties
Floyd County
Primary source water
surface water
UCMR 5 sampling
2025-04-07 to 2026-03-23 · 6 entry point(s) · water types: GW;SW
Service-area boundary
authoritative

PFOA ≥ 3 × its limit highest single result
PFOA 1–3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

  • Calhoun (GA1290000)
    Seller's highest results: PFOA 29 ppt · PFOS 29 ppt · HI 0.729 · detected: PFBA;PFBS;PFHpA;PFHxA;PFHxS;PFOA;PFOS;PFPeA
  • Adairsville (GA0150000)
    Seller's highest results: PFOA <MRL · PFOS <MRL · HI 0
  • Rome (GA1150002)
    Seller's highest results: PFOA 17.3 ppt · PFOS 10.9 ppt · HI 0.026 · detected: PFBA;PFBS;PFHpA;PFHxA;PFOA;PFOS;PFPeA

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)13.69.64
PFOS (ppt)9.28.054
Hazard Index0.0470.0221.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Sampling history

Sampled 2025-04-07 to 2026-03-23 · 6 entry point(s) · water types: GW;SW · 21 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2025-04-07Calhoun Intertie (SW)SE1<4<40.002none
2025-04-07Fulton Well #3 Plant (GW)SE1<4<40none
2025-04-07Kingston Road Well Plant (GW)SE15.66.90.004PFPeA 3.1
2025-04-07Old Mill Spring Plant (GW)SE1<4<40none
2025-04-07Rome (SW)SE19.3<40.006PFBA 5, PFHpA 3.5, PFHxA 8.4, PFPeA 9.4
2025-06-10Calhoun Intertie (SW)SE29.14.50.047PFBA 11.3, PFHxA 8, PFPeA 14.8
2025-06-10Rome (SW)SE211.14.50.007PFBA 5.1, PFHpA 4.5, PFHxA 9.3, PFPeA 11.1
2025-07-15Galey & Lord Brighton Plant (SW)SE1<4<40.007none
2025-09-10Calhoun Intertie (SW)SE3n/an/an/anone
2025-09-10Fulton Well #3 Plant (GW)SE2<4<40none
2025-09-10Galey & Lord Brighton Plant (SW)SE2<4<40.006none
2025-09-10Old Mill Spring Plant (GW)SE2<4<40none
2025-09-10Rome (SW)SE3n/an/an/anone
2025-09-15Kingston Road Well Plant (GW)SE2n/an/an/anone
2025-09-24Kingston Road Well Plant (GW)SE25.99.20.004PFHxA 3.2, PFPeA 3.4
2025-10-14Calhoun Intertie (SW)SE34.1<40.025PFBA 5.4, PFHxA 4, PFPeA 6.1
2025-10-14Rome (SW)SE34.4<40.003PFHxA 5, PFPeA 6.6
2025-12-09Calhoun Intertie (SW)SE4<4<40.016PFHxA 3.1, PFPeA 4.7
2025-12-09Rome (SW)SE413.69.10.03PFBA 10.9, PFHpA 5.7, PFHxA 15.2, PFPeA 23.4
2025-12-16Galey & Lord Brighton Plant (SW)SE3<4<40.004none
2026-03-23Galey & Lord Brighton Plant (SW)SE4<4<40.006none

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

540 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Calhoun Intertie facility 10001 · sample point 308 · surface water

CompoundMRL2025-04-07
SE1
2025-06-10
SE2
2025-09-10
SE3
2025-10-14
SE3
2025-12-09
SE4
PFBA5 ppt< 511.3–5.4< 5
PFBS3 ppt4.493.3–49.732.3
PFHxA3 ppt< 38–43.1
PFOA4 ppt< 49.1–4.1< 4
PFOS4 ppt< 44.5–< 4< 4
PFPeA3 ppt< 314.8–6.14.7
11Cl-PF3OUdS5 ppt< 5< 5–< 5< 5
4:2 FTS3 ppt< 3< 3–< 3< 3
6:2 FTS5 ppt< 5< 5–< 5< 5
8:2 FTS5 ppt< 5< 5–< 5< 5
9Cl-PF3ONS2 ppt< 2< 2–< 2< 2
ADONA3 ppt< 3< 3–< 3< 3
HFPO-DA5 ppt< 5< 5–< 5< 5
NEtFOSAA5 ppt< 5< 5< 5–< 5
NFDHA20 ppt< 20< 20–< 20< 20
NMeFOSAA6 ppt< 6< 6< 6–< 6
PFDA3 ppt< 3< 3–< 3< 3
PFDoA3 ppt< 3< 3–< 3< 3
PFEESA3 ppt< 3< 3–< 3< 3
PFHpA3 ppt< 3< 3–< 3< 3
PFHpS3 ppt< 3< 3–< 3< 3
PFHxS3 ppt< 3< 3–< 3< 3
PFMBA3 ppt< 3< 3–< 3< 3
PFMPA4 ppt< 4< 4–< 4< 4
PFNA4 ppt< 4< 4–< 4< 4
PFPeS4 ppt< 4< 4–< 4< 4
PFTA8 ppt< 8< 8< 8–< 8
PFTrDA7 ppt< 7< 7< 7–< 7
PFUnA2 ppt< 2< 2–< 2< 2
lithium9 µg/L< 9< 9< 9–< 9

Fulton Well #3 Plant facility 22907 · sample point 307 · groundwater

CompoundMRL2025-04-07
SE1
2025-09-10
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Galey & Lord Brighton Plant facility 18266 · sample point 306 · surface water

CompoundMRL2025-07-15
SE1
2025-09-10
SE2
2025-12-16
SE3
2026-03-23
SE4
PFBS3 ppt13.512.97.811.3
11Cl-PF3OUdS5 ppt< 5< 5< 5< 5
4:2 FTS3 ppt< 3< 3< 3< 3
6:2 FTS5 ppt< 5< 5< 5< 5
8:2 FTS5 ppt< 5< 5< 5< 5
9Cl-PF3ONS2 ppt< 2< 2< 2< 2
ADONA3 ppt< 3< 3< 3< 3
HFPO-DA5 ppt< 5< 5< 5< 5
NEtFOSAA5 ppt< 5< 5< 5< 5
NFDHA20 ppt< 20< 20< 20< 20
NMeFOSAA6 ppt< 6< 6< 6< 6
PFBA5 ppt< 5< 5< 5< 5
PFDA3 ppt< 3< 3< 3< 3
PFDoA3 ppt< 3< 3< 3< 3
PFEESA3 ppt< 3< 3< 3< 3
PFHpA3 ppt< 3< 3< 3< 3
PFHpS3 ppt< 3< 3< 3< 3
PFHxA3 ppt< 3< 3< 3< 3
PFHxS3 ppt< 3< 3< 3< 3
PFMBA3 ppt< 3< 3< 3< 3
PFMPA4 ppt< 4< 4< 4< 4
PFNA4 ppt< 4< 4< 4< 4
PFOA4 ppt< 4< 4< 4< 4
PFOS4 ppt< 4< 4< 4< 4
PFPeA3 ppt< 3< 3< 3< 3
PFPeS4 ppt< 4< 4< 4< 4
PFTA8 ppt< 8< 8< 8< 8
PFTrDA7 ppt< 7< 7< 7< 7
PFUnA2 ppt< 2< 2< 2< 2
lithium9 µg/L< 9< 9< 9< 9

Kingston Road Well Plant facility 02801 · sample point 302 · groundwater

CompoundMRL2025-04-07
SE1
2025-09-15
SE2
2025-09-24
SE2
PFBS3 ppt7.6–8.9
PFHxA3 ppt< 3–3.2
PFOA4 ppt5.6–5.9
PFOS4 ppt6.9–9.2
PFPeA3 ppt3.1–3.4
11Cl-PF3OUdS5 ppt< 5–< 5
4:2 FTS3 ppt< 3–< 3
6:2 FTS5 ppt< 5–< 5
8:2 FTS5 ppt< 5–< 5
9Cl-PF3ONS2 ppt< 2–< 2
ADONA3 ppt< 3–< 3
HFPO-DA5 ppt< 5–< 5
NEtFOSAA5 ppt< 5< 5–
NFDHA20 ppt< 20–< 20
NMeFOSAA6 ppt< 6< 6–
PFBA5 ppt< 5–< 5
PFDA3 ppt< 3–< 3
PFDoA3 ppt< 3–< 3
PFEESA3 ppt< 3–< 3
PFHpA3 ppt< 3–< 3
PFHpS3 ppt< 3–< 3
PFHxS3 ppt< 3–< 3
PFMBA3 ppt< 3–< 3
PFMPA4 ppt< 4–< 4
PFNA4 ppt< 4–< 4
PFPeS4 ppt< 4–< 4
PFTA8 ppt< 8< 8–
PFTrDA7 ppt< 7< 7–
PFUnA2 ppt< 2–< 2
lithium9 µg/L< 9< 9–

Old Mill Spring Plant facility 00961 · sample point 301 · groundwater

CompoundMRL2025-04-07
SE1
2025-09-10
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Rome facility 11865 · sample point 304 · surface water

CompoundMRL2025-04-07
SE1
2025-06-10
SE2
2025-09-10
SE3
2025-10-14
SE3
2025-12-09
SE4
PFBA5 ppt55.1–< 510.9
PFBS3 ppt11.813.9–5.160
PFHpA3 ppt3.54.5–< 35.7
PFHxA3 ppt8.49.3–515.2
PFOA4 ppt9.311.1–4.413.6
PFOS4 ppt< 44.5–< 49.1
PFPeA3 ppt9.411.1–6.623.4
11Cl-PF3OUdS5 ppt< 5< 5–< 5< 5
4:2 FTS3 ppt< 3< 3–< 3< 3
6:2 FTS5 ppt< 5< 5–< 5< 5
8:2 FTS5 ppt< 5< 5–< 5< 5
9Cl-PF3ONS2 ppt< 2< 2–< 2< 2
ADONA3 ppt< 3< 3–< 3< 3
HFPO-DA5 ppt< 5< 5–< 5< 5
NEtFOSAA5 ppt< 5< 5< 5–< 5
NFDHA20 ppt< 20< 20–< 20< 20
NMeFOSAA6 ppt< 6< 6< 6–< 6
PFDA3 ppt< 3< 3–< 3< 3
PFDoA3 ppt< 3< 3–< 3< 3
PFEESA3 ppt< 3< 3–< 3< 3
PFHpS3 ppt< 3< 3–< 3< 3
PFHxS3 ppt< 3< 3–< 3< 3
PFMBA3 ppt< 3< 3–< 3< 3
PFMPA4 ppt< 4< 4–< 4< 4
PFNA4 ppt< 4< 4–< 4< 4
PFPeS4 ppt< 4< 4–< 4< 4
PFTA8 ppt< 8< 8< 8–< 8
PFTrDA7 ppt< 7< 7< 7–< 7
PFUnA2 ppt< 2< 2–< 2< 2
lithium9 µg/L< 9< 9< 9–< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBS1878%93.3
2025-06-10
18.47–19.148.913.96093.3
PFPeA1850%23.4
2025-12-09
4.59–6.09<MRL6.614.823.4
PFHxA1844%15.2
2025-12-09
3.12–4.79<MRL59.315.2
PFOA1844%13.6
2025-12-09
3.51–5.73<MRL5.911.113.6
PFBA1828%11.3
2025-06-10
2.09–5.71<MRL510.911.3
PFOS1828%9.2
2025-09-24
1.9–4.79<MRL4.59.19.2
PFHpA1817%5.7
2025-12-09
0.76–3.26<MRL<MRL4.55.7

Never detected (23): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFDA, PFDoA, PFEESA, PFHpS, PFHxS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-17; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build e0e919e2a26a · 2026-10-18T04:09Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.