Lake Utility Services Inc North (8 Wps)

PFAS monitoring results for a public water system in Florida

FL3354883UCMR 5EPA monitoring data
10Highest PFOA result, ppt
14Highest PFOS result, ppt
0.377Highest Hazard Index
420Results
PWSID
FL3354883
State
Florida
System type
community water system (CWS)
Population served
24,798
City
Altamonte Springs
Counties
Lake County
Primary source water
groundwater
UCMR 5 sampling
2024-01-10 to 2024-07-09 · 7 entry point(s) · water types: GW
Service-area boundary
authoritative

PFOS ≥ 3 × its limit highest single result
PFOS ≥ 3 × its limit worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)109.74
PFOS (ppt)1413.54
Hazard Index0.3770.3611.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

No Florida PFAS drinking-water standard in effect or proposed as of 2026-10-17: No state PFAS drinking-water MCL. Ch. 2022-203 Laws of Fla. (s. 376.91) concerns contaminated-site cleanup target levels, not drinking water.

Sampling history

Sampled 2024-01-10 to 2024-07-09 · 7 entry point(s) · water types: GW · 15 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2024-01-10Amber Hill WTP (GW)SE1<440.002none
2024-01-10Clermont #1 WTP (GW)SE155.60.313PFHxA 3.4, PFPeA 4.1
2024-01-10Clermont #2 WTP (GW)SE1<45.10.002none
2024-01-10County Road 561 WTP (GW)SE1<4<40none
2024-01-10Lake Louisa WTP (GW)SE1n/an/an/anone
2024-01-10Lake Ridge WTP (GW)SE1<47.30.323none
2024-01-10Vistas WTP (GW)SE19.4130.346PFHxA 3.9, PFPeA 5
2024-02-20Lake Louisa WTP (GW)SE17.29.20.004PFPeA 3.5
2024-07-09Amber Hill WTP (GW)SE2<44.20.002none
2024-07-09Clermont #1 WTP (GW)SE2<44.30.002PFPeA 3.2
2024-07-09Clermont #2 WTP (GW)SE25.15.70.003PFPeA 3.1
2024-07-09County Road 561 WTP (GW)SE2<4<40none
2024-07-09Lake Louisa WTP (GW)SE256.50.003none
2024-07-09Lake Ridge WTP (GW)SE2<47.40.303none
2024-07-09Vistas WTP (GW)SE210140.377PFHxA 4.2, PFPeA 5.7

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

420 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Amber Hill WTP facility 10006 · sample point EP006 · groundwater

CompoundMRL2024-01-10
SE1
2024-07-09
SE2
PFBS3 ppt4.13.6
PFOS4 ppt44.2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Clermont #1 WTP facility 10003 · sample point EP003 · groundwater

CompoundMRL2024-01-10
SE1
2024-07-09
SE2
PFBS3 ppt5.43.3
PFHxA3 ppt3.4< 3
PFHxS3 ppt3.1< 3
PFOA4 ppt5< 4
PFOS4 ppt5.64.3
PFPeA3 ppt4.13.2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Clermont #2 WTP facility 10007 · sample point EP007 · groundwater

CompoundMRL2024-01-10
SE1
2024-07-09
SE2
PFBS3 ppt4.85.6
PFOA4 ppt< 45.1
PFOS4 ppt5.15.7
PFPeA3 ppt< 33.1
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

County Road 561 WTP facility 10004 · sample point EP004 · groundwater

CompoundMRL2024-01-10
SE1
2024-07-09
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Lake Louisa WTP facility 10001 · sample point EP001 · groundwater

CompoundMRL2024-01-10
SE1
2024-02-20
SE1
2024-07-09
SE2
PFBS3 ppt–8.55.2
PFOA4 ppt–7.25
PFOS4 ppt–9.26.5
PFPeA3 ppt–3.5< 3
11Cl-PF3OUdS5 ppt–< 5< 5
4:2 FTS3 ppt–< 3< 3
6:2 FTS5 ppt–< 5< 5
8:2 FTS5 ppt–< 5< 5
9Cl-PF3ONS2 ppt–< 2< 2
ADONA3 ppt–< 3< 3
HFPO-DA5 ppt–< 5< 5
NEtFOSAA5 ppt< 5–< 5
NFDHA20 ppt–< 20< 20
NMeFOSAA6 ppt< 6–< 6
PFBA5 ppt–< 5< 5
PFDA3 ppt–< 3< 3
PFDoA3 ppt–< 3< 3
PFEESA3 ppt–< 3< 3
PFHpA3 ppt–< 3< 3
PFHpS3 ppt–< 3< 3
PFHxA3 ppt–< 3< 3
PFHxS3 ppt–< 3< 3
PFMBA3 ppt–< 3< 3
PFMPA4 ppt–< 4< 4
PFNA4 ppt–< 4< 4
PFPeS4 ppt–< 4< 4
PFTA8 ppt< 8–< 8
PFTrDA7 ppt< 7–< 7
PFUnA2 ppt–< 2< 2
lithium9 µg/L< 9–< 9

Lake Ridge WTP facility 10002 · sample point EP002 · groundwater

CompoundMRL2024-01-10
SE1
2024-07-09
SE2
PFBS3 ppt5.26.1
PFHxS3 ppt3.23
PFOS4 ppt7.37.4
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Vistas WTP facility 10005 · sample point EP005 · groundwater

CompoundMRL2024-01-10
SE1
2024-07-09
SE2
PFBS3 ppt1213
PFHxA3 ppt3.94.2
PFHxS3 ppt3.43.7
PFOA4 ppt9.410
PFOS4 ppt1314
PFPeA3 ppt55.7
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

Statistics by compound

CompoundResultsDetectedHighest (date)Mean boundsKM medianP75P90P95
PFBS1486%13
2024-07-09
5.49–5.915.26.11213
PFOS1486%14
2024-07-09
6.16–6.745.67.41314
PFOA1443%10
2024-07-09
2.98–5.26<MRL5.19.410
PFPeA1443%5.7
2024-07-09
1.76–3.47<MRL3.555.7
PFHxS1436%3.7
2024-07-09
1.17–3.1<MRL3.13.43.7
PFHxA1421%4.2
2024-07-09
0.82–3.18<MRL<MRL3.94.2

Never detected (24): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFMBA, PFMPA, PFNA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-03 to 2026-06-09; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+

Data build 77d99d3b80c8 · 2026-10-18T04:10Z · UCMR 5 release Jul2026 · SDWIS 2026Q3. Data and methods.