- PWSID
- CA3610005
- State
- California
- System type
- community water system (CWS)
- Population served
- 7,038
- City
- Lake Arrowhead
- Counties
- San Bernardino County
- Primary source water
- surface water
- UCMR 5 sampling
- 2023-02-07 to 2024-07-10 · 2 entry point(s) · water types: MX;SW
- Service-area boundary
- authoritative
PFOA ≥ 3 × its limit highest single result
PFOA ≥ 3 × its limit worst entry-point average
Open on the California map · All California systems · All results
These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.
Water purchased from
- Clawa (CA3610114)
Seller not monitored under UCMR 5.
Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.
Compared with EPA's 2024 values
| Highest single result | Worst entry-point average* | Limit | |
|---|---|---|---|
| PFOA (ppt) | 14 | 12 | 4 |
| PFOS (ppt) | 7.2 | 5.92 | 4 |
| Hazard Index | 0.79 | 0.158 | 1.0† |
“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).
Compared with California guidance levels
| Highest single result | Worst entry-point average* | California | |
|---|---|---|---|
| PFHxS (ppt) | 3.3 | 0.82 | 3 (guidance) |
| PFOA (ppt) | 14 | 12 | 4 (guidance) |
| PFOS (ppt) | 7.2 | 5.92 | 4 (guidance) |
| PFBS (ppt) | 0 | 0 | 500 (guidance) |
| PFHxA (ppt) | 6.7 | 5.78 | 1,000 (guidance) |
Sum standards add the listed compounds within each sample (non-detects = 0). State compliance is normally judged on averages over time; these are screening comparisons.
Sampling history
Sampled 2023-02-07 to 2024-07-10 · 2 entry point(s) · water types: MX;SW · 11 sampling visits. PFAS in ppt (ng/L).
| Date | Entry point | Event | PFOA | PFOS | HI | Other detections |
|---|---|---|---|---|---|---|
| 2023-02-07 | Bernina TP (MX) | SE1 | 9.6 | 4.5 | 0 | PFHpA 4.1, PFHxA 4.7, PFPeA 3.5 |
| 2023-05-03 | Bernina TP (MX) | SE2 | 8.7 | 4.6 | 0 | PFHpA 3.8, PFHxA 4.6, PFPeA 3.7 |
| 2023-05-03 | Cedar Glen TP (SW) | SE1 | 12 | 5.9 | 0 | PFDA 3, PFHpA 5.6, PFHxA 6.6, PFPeA 3.9 |
| 2023-08-07 | Bernina TP (MX) | SE3 | n/a | n/a | n/a | none |
| 2023-08-07 | Cedar Glen TP (SW) | SE2 | 14 | 7.2 | 0.79 | PFDA 3.9, PFHpA 5.7, PFHxA 6.7, PFPeA 4.5 |
| 2023-11-07 | Bernina TP (MX) | SE3 | 9.8 | 4.8 | 0 | PFHpA 4.7, PFHxA 5.4, PFPeA 3.6 |
| 2023-11-07 | Bernina TP (MX) | SE4 | 11 | 4.3 | 0 | PFHpA 4.3, PFHxA 5.3, PFPeA 3.9 |
| 2023-11-07 | Cedar Glen TP (SW) | SE3 | n/a | n/a | 0 | none |
| 2024-01-31 | Cedar Glen TP (SW) | SE3 | 11 | 5.6 | 0 | PFDA 3.4, PFHpA 4.8, PFHxA 5, PFPeA 3.9 |
| 2024-03-06 | Cedar Glen TP (SW) | SE4 | n/a | n/a | n/a | none |
| 2024-07-10 | Cedar Glen TP (SW) | SE4 | 11 | 5 | 0 | PFHpA 4.4, PFHxA 4.8, PFPeA 3.7 |
“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).
All results by entry point
240 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.
Bernina TP facility 10002 · sample point EP002 · MX
| Compound | MRL | 2023-02-07 SE1 | 2023-05-03 SE2 | 2023-08-07 SE3 | 2023-11-07 SE3 | 2023-11-07 SE4 |
|---|---|---|---|---|---|---|
| PFHpA | 3 ppt | 4.1 | 3.8 | – | 4.7 | 4.3 |
| PFHxA | 3 ppt | 4.7 | 4.6 | – | 5.4 | 5.3 |
| PFOA | 4 ppt | 9.6 | 8.7 | – | 9.8 | 11 |
| PFOS | 4 ppt | 4.5 | 4.6 | – | 4.8 | 4.3 |
| PFPeA | 3 ppt | 3.5 | 3.7 | – | 3.6 | 3.9 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | – | < 5 | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 | – | < 5 | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 | – | < 5 | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | – | < 2 | < 2 |
| ADONA | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 | – | < 5 | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | < 5 | – | < 5 |
| NFDHA | 20 ppt | < 20 | < 20 | – | < 20 | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | < 6 | – | < 6 |
| PFBA | 5 ppt | < 5 | < 5 | – | < 5 | < 5 |
| PFBS | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFDA | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFHxS | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 | – | < 3 | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 | – | < 4 | < 4 |
| PFNA | 4 ppt | < 4 | < 4 | – | < 4 | < 4 |
| PFPeS | 4 ppt | < 4 | < 4 | – | < 4 | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | < 8 | – | < 8 |
| PFTrDA | 7 ppt | < 7 | < 7 | < 7 | – | < 7 |
| PFUnA | 2 ppt | < 2 | < 2 | – | < 2 | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | < 9 | – | < 9 |
Cedar Glen TP facility 10004 · sample point EP004 · surface water
| Compound | MRL | 2023-05-03 SE1 | 2023-08-07 SE2 | 2023-11-07 SE3 | 2024-01-31 SE3 | 2024-03-06 SE4 | 2024-07-10 SE4 |
|---|---|---|---|---|---|---|---|
| PFDA | 3 ppt | 3 | 3.9 | – | 3.4 | – | < 3 |
| PFHpA | 3 ppt | 5.6 | 5.7 | – | 4.8 | – | 4.4 |
| PFHxA | 3 ppt | 6.6 | 6.7 | – | 5 | – | 4.8 |
| PFHxS | 3 ppt | < 3 | 3.3 | < 3 | – | – | < 3 |
| PFNA | 4 ppt | < 4 | 4.6 | – | < 4 | – | < 4 |
| PFOA | 4 ppt | 12 | 14 | – | 11 | – | 11 |
| PFOS | 4 ppt | 5.9 | 7.2 | – | 5.6 | – | 5 |
| PFPeA | 3 ppt | 3.9 | 4.5 | – | 3.9 | – | 3.7 |
| 11Cl-PF3OUdS | 5 ppt | < 5 | < 5 | < 5 | – | – | < 5 |
| 4:2 FTS | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| 6:2 FTS | 5 ppt | < 5 | < 5 | < 5 | – | – | < 5 |
| 8:2 FTS | 5 ppt | < 5 | < 5 | < 5 | – | – | < 5 |
| 9Cl-PF3ONS | 2 ppt | < 2 | < 2 | < 2 | – | – | < 2 |
| ADONA | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| HFPO-DA | 5 ppt | < 5 | < 5 | < 5 | – | – | < 5 |
| NEtFOSAA | 5 ppt | < 5 | < 5 | < 5 | – | < 5 | – |
| NFDHA | 20 ppt | < 20 | < 20 | < 20 | – | – | < 20 |
| NMeFOSAA | 6 ppt | < 6 | < 6 | < 6 | – | < 6 | – |
| PFBA | 5 ppt | < 5 | < 5 | < 5 | – | – | < 5 |
| PFBS | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| PFDoA | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| PFEESA | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| PFHpS | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| PFMBA | 3 ppt | < 3 | < 3 | < 3 | – | – | < 3 |
| PFMPA | 4 ppt | < 4 | < 4 | < 4 | – | – | < 4 |
| PFPeS | 4 ppt | < 4 | < 4 | < 4 | – | – | < 4 |
| PFTA | 8 ppt | < 8 | < 8 | < 8 | – | < 8 | – |
| PFTrDA | 7 ppt | < 7 | < 7 | < 7 | – | < 7 | – |
| PFUnA | 2 ppt | < 2 | < 2 | < 2 | – | – | < 2 |
| lithium | 9 µg/L | < 9 | < 9 | < 9 | – | < 9 | – |
Statistics by compound
| Compound | Results | Detected | Highest (date) | Mean bounds | KM median | P75 | P90 | P95 |
|---|---|---|---|---|---|---|---|---|
| PFHpA | 8 | 100% | 5.7 2023-08-07 | 4.67–4.67 | 4.4 | 4.8 | 5.7 | 5.7 |
| PFHxA | 8 | 100% | 6.7 2023-08-07 | 5.39–5.39 | 5 | 5.4 | 6.7 | 6.7 |
| PFOA | 8 | 100% | 14 2023-08-07 | 10.89–10.89 | 11 | 11 | 14 | 14 |
| PFOS | 8 | 100% | 7.2 2023-08-07 | 5.24–5.24 | 4.8 | 5.6 | 7.2 | 7.2 |
| PFPeA | 8 | 100% | 4.5 2023-08-07 | 3.84–3.84 | 3.7 | 3.9 | 4.5 | 4.5 |
| PFDA | 8 | 38% | 3.9 2023-08-07 | 1.29–3.16 | <MRL | 3 | 3.9 | 3.9 |
| PFHxS | 8 | 12% | 3.3 2023-08-07 | 0.41–3.04 | <MRL | <MRL | 3.3 | 3.3 |
| PFNA | 8 | 12% | 4.6 2023-08-07 | 0.57–4.08 | <MRL | <MRL | 4.6 | 4.6 |
Never detected (22): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDoA, PFEESA, PFHpS, PFMBA, PFMPA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.
Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.
Sources
- EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-17; data summary dated Jul 2026)