Marin Municipal Water District

PFAS monitoring results for a public water system in California

CA2110002UCMR 5EPA monitoring data
<MRLHighest PFOA result, ppt
<MRLHighest PFOS result, ppt
0Highest Hazard Index
275Results
PWSID
CA2110002
State
California
System type
community water system (CWS)
Population served
188,116
City
Corte Madera
Counties
Marin County
Primary source water
surface water
UCMR 5 sampling
2023-07-10 to 2024-07-08 · 3 entry point(s) · water types: GW;SW
Service-area boundary
authoritative

No PFAS detected highest single result
No PFAS detected worst entry-point average

These are monitoring results collected under EPA's Fifth Unregulated Contaminant Monitoring Rule (UCMR 5) at entry points, where treated water enters the distribution system; they are not tap-water samples. They are not compliance determinations: compliance with EPA's 2024 PFAS limits is judged on running annual averages of compliance monitoring, required from 2029, so a single UCMR 5 result at or above a limit is not a violation. “< MRL” means the compound was not quantified at EPA's minimum reporting level; it does not mean zero.

Water purchased from

Seller results are the seller's own entry-point samples, not measurements of this system's water. This system's own samples (below) may reflect purchased water, its own sources, or both.

Compared with EPA's 2024 values

Highest single resultWorst entry-point average*Limit
PFOA (ppt)<MRL04
PFOS (ppt)<MRL04
Hazard Index001.0†

“<MRL” = every result for the compound was below its reporting limit. * Mean of all samples at each entry point with non-detects = 0 (EPA compliance convention; the Hazard Index also uses non-detects = 0); a screening comparison, not a formal running annual average. † Rescission proposed May 2026. PFOA/PFOS MCL 4 ppt (2024 NPDWR, in effect). PFHxS, PFNA, HFPO-DA (10 ppt each) and the Hazard Index (1.0) are 2024 NPDWR values; EPA proposed rescinding them on 18 May 2026 (comment period closed 20 Jul 2026).

Compared with California guidance levels

Highest single resultWorst entry-point average*California
PFHxS (ppt)003 (guidance)
PFOA (ppt)004 (guidance)
PFOS (ppt)004 (guidance)
PFBS (ppt)00500 (guidance)
PFHxA (ppt)001,000 (guidance)

Sum standards add the listed compounds within each sample (non-detects = 0). State compliance is normally judged on averages over time; these are screening comparisons.

Sampling history

Sampled 2023-07-10 to 2024-07-08 · 3 entry point(s) · water types: GW;SW · 13 sampling visits. PFAS in ppt (ng/L).

DateEntry pointEventPFOAPFOSHIOther detections
2023-07-10Bon Tempe TP (SW)SE1n/an/an/anone
2023-08-02Bon Tempe TP (SW)SE1<4<40none
2023-08-07Ignacio Pump Station (GW)SE1<4<40none
2023-09-11San Geronimo TP (SW)SE1n/an/an/anone
2023-10-09Bon Tempe TP (SW)SE2<4<40none
2023-12-12San Geronimo TP (SW)SE2<4<40none
2024-01-08Bon Tempe TP (SW)SE3<4<40none
2024-02-13Ignacio Pump Station (GW)SE2<4<40none
2024-03-11San Geronimo TP (SW)SE3<4<40none
2024-04-08Bon Tempe TP (SW)SE4n/an/an/anone
2024-05-13Bon Tempe TP (SW)SE4<4<40none
2024-06-10San Geronimo TP (SW)SE4<4<40none
2024-07-08San Geronimo TP (SW)SE4n/an/an/anone

“<4” = not detected at the reporting limit shown; “n/a” = not analyzed in that sample. Highlighted = at or above the 4 ppt MCL. HI computed per sample with non-detects as 0. Other detections lists every other quantified compound (lithium in µg/L).

All results by entry point

275 results. Each column is one sampling visit (date and UCMR 5 sample event). A number is a measured concentration; “< 4” = below the minimum reporting level shown; “–” = not analyzed in that visit. PFAS in ppt (ng/L); lithium in µg/L.

Bon Tempe TP facility 91004 · sample point 2110002004 · surface water

CompoundMRL2023-07-10
SE1
2023-08-02
SE1
2023-10-09
SE2
2024-01-08
SE3
2024-04-08
SE4
2024-05-13
SE4
11Cl-PF3OUdS5 ppt–< 5< 5< 5–< 5
4:2 FTS3 ppt–< 3< 3< 3–< 3
6:2 FTS5 ppt–< 5< 5< 5–< 5
8:2 FTS5 ppt–< 5< 5< 5–< 5
9Cl-PF3ONS2 ppt–< 2< 2< 2–< 2
ADONA3 ppt–< 3< 3< 3–< 3
HFPO-DA5 ppt–< 5< 5< 5–< 5
NEtFOSAA5 ppt< 5–< 5< 5< 5–
NFDHA20 ppt–< 20< 20< 20–< 20
NMeFOSAA6 ppt< 6–< 6< 6< 6–
PFBA5 ppt–< 5< 5< 5–< 5
PFBS3 ppt–< 3< 3< 3–< 3
PFDA3 ppt–< 3< 3< 3–< 3
PFDoA3 ppt–< 3< 3< 3–< 3
PFEESA3 ppt–< 3< 3< 3–< 3
PFHpA3 ppt–< 3< 3< 3–< 3
PFHpS3 ppt–< 3< 3< 3–< 3
PFHxA3 ppt–< 3< 3< 3–< 3
PFHxS3 ppt–< 3< 3< 3–< 3
PFMBA3 ppt–< 3< 3< 3–< 3
PFMPA4 ppt–< 4< 4< 4–< 4
PFNA4 ppt–< 4< 4< 4–< 4
PFOA4 ppt–< 4< 4< 4–< 4
PFOS4 ppt–< 4< 4< 4–< 4
PFPeA3 ppt–< 3< 3< 3–< 3
PFPeS4 ppt–< 4< 4< 4–< 4
PFTA8 ppt< 8–< 8< 8< 8–
PFTrDA7 ppt< 7–< 7< 7< 7–
PFUnA2 ppt–< 2< 2< 2–< 2
lithium9 µg/L< 9–< 9< 9< 9–

Ignacio Pump Station facility 91005 · sample point 2110002005 · groundwater

CompoundMRL2023-08-07
SE1
2024-02-13
SE2
11Cl-PF3OUdS5 ppt< 5< 5
4:2 FTS3 ppt< 3< 3
6:2 FTS5 ppt< 5< 5
8:2 FTS5 ppt< 5< 5
9Cl-PF3ONS2 ppt< 2< 2
ADONA3 ppt< 3< 3
HFPO-DA5 ppt< 5< 5
NEtFOSAA5 ppt< 5< 5
NFDHA20 ppt< 20< 20
NMeFOSAA6 ppt< 6< 6
PFBA5 ppt< 5< 5
PFBS3 ppt< 3< 3
PFDA3 ppt< 3< 3
PFDoA3 ppt< 3< 3
PFEESA3 ppt< 3< 3
PFHpA3 ppt< 3< 3
PFHpS3 ppt< 3< 3
PFHxA3 ppt< 3< 3
PFHxS3 ppt< 3< 3
PFMBA3 ppt< 3< 3
PFMPA4 ppt< 4< 4
PFNA4 ppt< 4< 4
PFOA4 ppt< 4< 4
PFOS4 ppt< 4< 4
PFPeA3 ppt< 3< 3
PFPeS4 ppt< 4< 4
PFTA8 ppt< 8< 8
PFTrDA7 ppt< 7< 7
PFUnA2 ppt< 2< 2
lithium9 µg/L< 9< 9

San Geronimo TP facility 91011 · sample point 2110002011 · surface water

CompoundMRL2023-09-11
SE1
2023-12-12
SE2
2024-03-11
SE3
2024-06-10
SE4
2024-07-08
SE4
11Cl-PF3OUdS5 ppt–< 5< 5< 5–
4:2 FTS3 ppt–< 3< 3< 3–
6:2 FTS5 ppt–< 5< 5< 5–
8:2 FTS5 ppt–< 5< 5< 5–
9Cl-PF3ONS2 ppt–< 2< 2< 2–
ADONA3 ppt–< 3< 3< 3–
HFPO-DA5 ppt–< 5< 5< 5–
NEtFOSAA5 ppt< 5< 5< 5–< 5
NFDHA20 ppt–< 20< 20< 20–
NMeFOSAA6 ppt< 6< 6< 6–< 6
PFBA5 ppt–< 5< 5< 5–
PFBS3 ppt–< 3< 3< 3–
PFDA3 ppt–< 3< 3< 3–
PFDoA3 ppt–< 3< 3< 3–
PFEESA3 ppt–< 3< 3< 3–
PFHpA3 ppt–< 3< 3< 3–
PFHpS3 ppt–< 3< 3< 3–
PFHxA3 ppt–< 3< 3< 3–
PFHxS3 ppt–< 3< 3< 3–
PFMBA3 ppt–< 3< 3< 3–
PFMPA4 ppt–< 4< 4< 4–
PFNA4 ppt–< 4< 4< 4–
PFOA4 ppt–< 4< 4< 4–
PFOS4 ppt–< 4< 4< 4–
PFPeA3 ppt–< 3< 3< 3–
PFPeS4 ppt–< 4< 4< 4–
PFTA8 ppt< 8< 8< 8–< 8
PFTrDA7 ppt< 7< 7< 7–< 7
PFUnA2 ppt–< 2< 2< 2–
lithium9 µg/L< 9< 9< 9< 9–

Statistics by compound

No compound was detected; every result is below its reporting limit, so no Kaplan–Meier statistics can be estimated.

Never detected (30): 11Cl-PF3OUdS, 4:2 FTS, 6:2 FTS, 8:2 FTS, 9Cl-PF3ONS, ADONA, HFPO-DA, NEtFOSAA, NFDHA, NMeFOSAA, PFBA, PFBS, PFDA, PFDoA, PFEESA, PFHpA, PFHpS, PFHxA, PFHxS, PFMBA, PFMPA, PFNA, PFOA, PFOS, PFPeA, PFPeS, PFTA, PFTrDA, PFUnA, lithium.

Left-censored Kaplan–Meier statistics (Helsel 2005; Helsel & Lee 2006, NADA for R). Units: ppt; lithium µg/L. Each compound has one reporting limit, so the Kaplan–Meier mean equals the upper mean bound (non-detects at the MRL); the lower bound sets non-detects to 0. “<MRL” = the percentile falls below the reporting limit and cannot be estimated. These describe this system's UCMR 5 samples, not population estimates.

Sources

  • EPA UCMR 5 occurrence data text files (UCMR5_All.txt; samples 2023-01-09 to 2026-06-17; data summary dated Jul 2026)
  • EPA SDWIS via ECHO SDWA downloads, quarter 2026Q3
  • EPA Public Water System Service Areas v3 (Mar 2026)
  • US Census Bureau cartographic boundary counties 1:500k, 2024
  • EPA/USGS NHDPlus V2 (medium resolution) flowlines, Strahler order 2+